3 calibration, Calibration process, Calibration parameters – Flowserve 400MD Logix User Manual

Page 78

Advertising
background image

CAUTION:

The configurator application can be used to perform the calibration procedures. The software application is not a calibrated

measurement source. It is a digital diagnostic tool that provides verification of device parameter values.

Calibration Process

In general, calibration procedures follow these processes:

1. Prepare the device. (Note: The transducer function block must be out-of-service in order to perform any calibration.)

2. Write to CALIBRATE.

3. Observe the positioner performance.

The calibration parameter values and calibration commands are written to the device using a fieldbus configuration application, (such as the
NI-FBUS Configurator).

Alternatively, use the Re-Cal button on the Logix 3400MD digital positioner to perform the stroke calibration. Confirm that positioner is con-
figured properly, then proceed.

1. Prepare the device and safe the area for the removal of the main housing cover.

2. Remove the cover.

3. Press and hold the Re-Cal button for at least five seconds to initiate the stroke calibration. (NOTE: The transducer block must be out-of-service before the
Re-Cal button will be active.) If Auto Tune is selected, this will also auto tune the positioner response.

4. Replace cover and return to operation. (Refer to Logix 3400MD Digital Positioner IOM for more details.)

9.3 Calibration

The output position of the Logix 3400MD digital positioner is calibrated using the transducer block CALIBRATE parameter. The positioner performance must
be verified by the operator.

Calibration Parameters

Table 9.1 lists transducer block parameters and their values used in the calibration procedures.

Table 9.1 Transducer Block Calibration Parameters

Parameter

Description

Value - Meaning

Comments

MODE_BLK

The operating mode

of the transducer

block

Permitted modes:

The transducer block must be in the OOS mode to perform Logix

3400MD digital positioner calibration.

Auto — Auto (target mode)
OOS — Out of Service

CALIBRATE

One-byte value

which selects the

calibration

operation to be

performed.

0 Normal operation. Valve tracks

Calibration and correction commands are executed when the

command is written.

FINAL_VALUE
1 Initiates stroke calibration. Closes valve.

2 Initiates actuator pressure
transducers calibration.
3 Moving valve closed position

Messages only

4 Moving valve to open position
5 Calibrating Supply
6 Calibrating actuator sensor - closed
7 Calibrating actuator sensor - open
8 Monitoring of Re-Cal button.
9 Error occurred during calibration
10 Inner-loop offset adjustment

Nulls the spool block

Logix 3400MD Digital Positioner LGENIM3405-02 11/13