NOTE: SIMULATE.ENABLE can only be set TRUE when the Simulate dip switch is in the “On” position when the device is powered up or a pro-
cessor restart is issued.

READBACK Parameter The value and status of READBACK will come from either the OUT parameter or SIMULATE.SIMULATE, determined by
the state of the OUT_READBACK feature in the Resource Block. READBACK is in XD units.

When RS.FEATURE.OUT_READBACK is set TRUE, SIMULATE.SIMULATE is used for READBACK. When FEATURE.OUT_READBACK is FALSE, OUT
will be used for READBACK.

NOTE: The default value for RS.FEATURE.OUT_READBACK is FALSE. With the Logix 3400MD, this feature should always be set TRUE to allow
the transducer block position value to be the source of READBACK.

READBACK_OUT ALLOWS THE USER A LINKABLE PARAMETER FOR VALVE POSITION.

PV Parameter The PV value is simply the READBACK value, re-scaled from XD units to PV units. PV status is copied directly from READBACK

status.

8.9 Digital Output Function Block

DO Block Description

Operates according to Section 10.18

Table 8.10 DO Function Block Parameter List

Index Origin

Name

Store

Date Type

Default Value

0

STND DISCRETE_OUTPUT_BLOCK

SRW

Record

BLOCK

0

1

STND ST_REV

SR

Simple

UNSIGNED16

0

2

STND TAG_DESC

SRW

Simple

OCTET_STRING

“ “

3

STND STRATEGY

SRW

Simple

UNSIGNED16

0

4

STND ALERT_KEY

SRW

Simple

UNSIGNED8

0

5

STND MODE_BLK

SRW

Record

MODE

0x01;0x01;0x79;0x30

6

STND BLOCK_ERR

R

Simple

BIT_STRING

0

7

STND PV_D

R

Record

DISC_S

0;0

8

STND SP_D

NRW

Record

DISC_S

DO_VAL_SP_D_STATUS;DO_VAL_SP_D_VALUE

9

STND OUT_D

NRWO Record

DISC_S

0x1C;0

10 STND SIMULATE_D

RW

Record

SIM_DISC

0;0;0;0;1

11 STND PV_STATE

SRW

Simple

UNSIGNED16

0

12 STND XD_STATE

SRW

Simple

UNSIGNED16

0

13 STND GRANT_DENY

RW

Record

ACCESS_PERM

0;0

14 STND IO_OPTS|IO_OPTS_DO

SRW

Simple

BIT_STRING

0

15 STND STATUS_OPTS|STATUS_OPTS_DO

SRW

Simple

BIT_STRING

0

16 STND READBACK_D

R

Record

DISC_S

0;0

17 STND CAS_IN_D

RWI

Record

DISC_S

0x1C;0

18 STND CHANNEL

SRW

Simple

UNSIGNED16

0

19 STND FSTATE_TIME

SRW

Simple

FLOATING_POINT

0

20 STND FSTATE_VAL_D

SRW

Simple

UNSIGNED8

0

21 STND BKCAL_OUT_D

RO

Record

DISC_S

0;0

22 STND RCAS_IN_D

RW

Record

DISC_S

0x1C;0

23 STND SHED_OPT

SRW

Simple

UNSIGNED8

0

24 STND RCAS_OUT_D

R

Record

DISC_S

0;0

25 STND UPDATE_EVT

RW

Record

ALARM_EVENT

0;0;0,0;0;0;9;0

26 STND BLOCK_ALM

RW

Record

ALARM_DISC

0;0;0,0;0;0;0;8;0;0

Block

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

47

Advertising