AO Block Diagram

Figure 8.3 is a block diagram showing the key components of the AO function block.

Figure 8.3 AO Function Block Diagram

Clearing Block Configuration Errors

Block configuration errors prevent the block from leaving OOS mode. The parameter BLOCK_ERR will show whether a block configuration error
is present. Table 10.7 is a list of parameters that can cause the status of CONFIGURATION ERROR to be set in the AO BLOCK_ERR parameter.
NOTE: CONFIGURATION ERROR can only be cleared if the function block is being executed. One way of determining block execution is by per-
forming a series two or three reads of the BLOCK_TEST parameter and confirming that the first byte of the parameter is incrementing. This will
work if the execute rate is fast relative to the speed of reading BLOCK_TEST. A very slowly executing block may not appear to execute because
block parameters are updated only when the block executes.

Mode-restricted Write Operations

Table 8.7 lists the AO block parameters which may be write restricted based upon the block’s mode. Listed in the table are the TARGET and/or
ACTUAL modes required for the write to be accepted. Other limitations listed in the last column must also be met.

SIMULATE, READBACK and PV Determination

In the AO Function Block, these three parameters provide the values and status of the actuator position, where SIMULATE (or optionally OUT)
generates the READBACK parameter and READBACK is then re-scaled to produce the PV.

The following sub-sections describe each of these parameters.

SIMULATE Parameter SIMULATE is the interface parameter between the AO and the Transducer Function Blocks. Each time the AO block ex-
ecutes, SIMULATE.TRANSDUCER is updated with the FINAL_POSITION_VALUE from the transducer block.

When the SIMULATE.ENABLE is FALSE, SIMULATE.TRANSDUCER is copied into SIMULATE. SIMULATE. When SIMULATE.ENABLE is TRUE,
SIMULATE.SIMULATE is not updated with SIMULATE.TRANSDUCER and the user may write a value and status to SIMULATE.SIMULATE.

AO Block Diagram

Figure 8.3 AO Function Block Diagram

Transducer Block 1

Transducer Block 2

OUT

Convert

PV SCALE

MODE

Select

SP RATE UP

ACTUAL

TARGET
PERMITED

PV

CAS IN

RCAS IN

Setpoint

Limiting

SP RATE DN

SP HI LIM

SP LO LIM

SP

(Read)

XD SCALE

FaultState

Check

FSTATE TIME

FSTATE_VAL

BKCAL OUT

RCAS OUT

SIMULATE:

TRANSDUCER

SIMULATE

ENABLE

READBACK

PV

Convert

U

SE PV

FOR BKCAL

BLOCK ALM

SHED OPT

UPDATE EVT

STATUS OPTS

AUTO

RCAS

F

ROM

O

UT

C

ONVERT

LO

AUTO

MAN

FaultState to Value

Rate

Limiting

Last SP

FSTATE

VALUE

MAN
LO

SP

(Write)

Setpoint

Tracking

PV

TARGET

ACTUAL

WSP

Status

Calculation

Invert

Incr. to Close

fstate: Active

Time OUT

Timer

SHED RCAS

Targ to MAN on Bad IN

CHANNEL

Transducer Block n

SHED OPT

OUT

T

O

O

UT

P

ARAMETER

CAS

ACTUAL

ACTUAL

TARGET

ACTUAL

SP Track Ret. Tgt

SP PV Track in Man.

SP PV Track LO IMAN

RCAS timeout

RCAS timeout

RCAS timeout

CAS

RCAS

IMAN

RS Feature_Sel

Out_Readback On

READBACK_Out

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

46

Advertising