Table 10.16 Transducer Block Signature Parameters

Parameter

Description

Value-Meaning

Comments

MODE_BLK

The operating mode of the

Transducer block

Permitted Modes: Auto-Auto

(target mode)

OOS-Out of Service

The transducer block must be in the OOS mode to perform

a Signature

SIG_START

Beginning position point for signature

to start.

Value is in percent and should be set in the

range of -10% to 110%.

SIG_STOP

Ending position point for signature. Value is in percent and should be set in the

range of -10% to 110%.

RAMP_RATE

Desired time for ramp signature in

seconds..

Minimum value is 1

RAMP_RATE is only used in the ramp signature. This is ignored

in step signatures.

SIG_HOLD

Time in seconds after step or ramp

that the the system will log data.

SIG_FLAGS

Byte value which select

Which signature options

Are used

0x01 RUN/BEGIN_SIG

0x02 SIG_COMPLETE

0x04 TEST REPEAT MODE

0x08 RUN RAMP

0x10 VALVE_

0x20 END OF DAT

0x40 TEST DAC MODE

0x80 RUN PST

Select to initiate the signature

Status set when signature is complete

Select to run a ramp signature otherwise it defaults to a step

signiature.

Initializes valve for signature capture (read only

End of signiature data encountered when uploading.

Select for special DAC mode

Run Partial Stroke Test (PST)

SIG_INDEX

Pointer used for data

transfer

Write the desired packet

value.

Writing any value to SIG_INDEX will initiate a sig data transfer

and will populate the SIG_DATAn parameters in the XDTB_

TECH block.

SIG_DATAn

Arrays to hold the signature data after

transfer from controller board.

The DIG_DATAn parameters are populated with the latest

signature data when a write to the SIG_INDEX parameter is

done.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13