Fail-safe handling, Ao block parameter list – Flowserve 400MD Logix User Manual

Page 45

Advertising
background image

The OUT parameter of the AO block is used to set the FINAL_POSITION_VALUE in the transducer block, as modified by the FINAL_VALUE_
RANGE.

READBACK_OUT tracks the valve position in percent.

Fail-safe Handling

The fail-safe parameters determine the response of an output block to the following conditions. FSTATE_TIME is the number of seconds
without communication or with Initiate Fail Safe at the CAS_IN status, required to put this block into the fail safe state. The FAULT_STATE
parameter of the resource block may also put this block into the fail safe state. The Failsafe Type I/O option determines whether the action is
simply to hold, or to move to FSTATE_VAL.

The Target to Manual if IFS I/O option may be used to latch the fail safe state when IFS appears in the CAS_IN status. This will cause a fail-safe
block alarm. After the cause of the IFS status is removed, the target mode may be returned manually to CAS mode when it is safe to do so
Section 10.17 described how to setup the fail-safe handling.

AO Block Parameter List

Table 8.8 lists the block parameters and default values for the AO function block.

Table 8.9 AO Function Block Parameter List

Index Origin

Name

Store

Date Type

Default Value

0

STND ANALOG_OUTPUT_BLOCK

SRW

Record

BLOCK

0

1

STND ST_REV

SR

Simple

UNSIGNED16

0

2

STND TAG_DESC

SRW

Simple

OCTET_STRING

“ “

3

STND STRATEGY

SRW

Simple

UNSIGNED16

0

4

STND ALERT_KEY

SRW

Simple

UNSIGNED8

0

5

STND MODE_BLK

SRW

Record

MODE

0x01;0x01;0x79;0x10

6

STND BLOCK_ERR

R

Simple

BIT_STRING

0

7

STND PV

R

Record

FLOAT_S

0;0.0

8

STND SP

NRW

Record

FLOAT_S

AO_VAL_SP_STATUS;AO_VAL_SP_VALUE

9

STND OUT

NRWO Record

FLOAT_S

0x80;0.0

10 STND SIMULATE

RW

Record

SIM_FLOAT

0;0.0;0;0.0;1

11 STND PV_SCALE

SRW

Record

SCALE

100.0;0.0;0;0

12 STND XD_SCALE

SRW

Record

SCALE

100.0;0.0;0;0

13 STND GRANT_DENY

RW

Record

ACCESS_PERM

0;0

14 STND IO_OPTS|IO_OPTS_AO

SRW

Simple

BIT_STRING

0

15 STND STATUS_OPTS|STATUS_OPTS_AO

SRW

Simple

BIT_STRING

0

16 STND READBACK

R

Record

FLOAT_S

0x80;0.0

17 STND CAS_IN

NRWI Record

FLOAT_S

0xC3;0.0

18 STND SP_RATE_DN

SRW

Simple

FLOATING_POINT

FLT_MAX

19 STND SP_RATE_UP

SRW

Simple

FLOATING_POINT

FLT_MAX

20 STND SP_HI_LIM

SRW

Simple

FLOATING_POINT

100

21 STND SP_LO_LIM

SRW

Simple

FLOATING_POINT

0

22 STND CHANNEL

SRW

Simple

UNSIGNED16

1

23 STND FSTATE_TIME

SRW

Simple

FLOATING_POINT

0

24 STND FSTATE_VAL

SRW

Simple

FLOATING_POINT

0

25 STND BKCAL_OUT

RO

Record

FLOAT_S

0xcc;0.0

26 STND RCAS_IN

NRW

Record

FLOAT_S

0x1C;0.0

27 STND SHED_OPT

SRW

Simple

UNSIGNED8

0

28 STND RCAS_OUT

R

Record

FLOAT_S

0xcc;0.0

29 STND UPDATE_EVT

RW

Record

ALARM_EVENT

0;0;0,0;0;0;9;0

30 STND BLOCK_ALM

RW

Record

ALARM_DISC

0;0;0,0;0;0;0;8;0;0

31 MFG

WSP

RW

Record

FLOAT_S

0,0.0

32 MFG

READBACK_OUT

RO

Record

FLOAT_S

0x80;0.0

33 MFG

AO_BLOCK_TEST

R

Array

UNSIGNED8

0,0,0,0,0,0,0,0

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

45