6 clearing block configuration errors, Clearing block configuration errors – Flowserve 400MD Logix User Manual

Page 86

Advertising
background image

AO block is in the correct

mode but does not seem to

be operating

1. Simulation active.

1. Disable simulation. See Sub-section 10.8 for procedure.

2. The block has not been configured to

execute. It is neither in the function block

schedule in the system management in-

formation base, nor is it linked to another

executing block via the next block to

execute field in the block record (relative

parameter index 0).

2. Build and download an execution schedule for the block including links to

and from AO block with other function blocks.

3. The second element of BLOCK_TEST is

not zero.

3. Write all zeroes to the second element of the BLOCK_TEST parameter.

10.6 Clearing Block Configuration Errors

Clearing Block Configuration Errors

Table 10.8 and Table 10.9 list the parameters in the AO and PID blocks which can cause the status bit of block configuration error to be set in
their respective BLOCK_ERR parameters. The tables also provide the initial values and the valid range for the parameters.

NOTE: Block configuration errors can only be cleared if the function block is being executed (running). One way of determining block execution
is by doing a series of two or three reads of the BLOCK_TEST parameter and confirming that the first byte of the parameter is incrementing.
This will work if the execute rate is fast relative to the speed of reading BLOCK_TEST. A very slowly executing block may not appear to execute
because block parameters are updated only when the block executes.

Table 10.8 AO Block Parameters

Parameter

Initial Value

Valid Range

Corrective Action

ALERT_KEY

0

non-zero

Initial value is a configuration error. Set value to non-zero number.

SIMULATE

1(disabled)

1-2 (disabled-enabled) Set value in valid range.

XD_SCALE

0to100

EU_100 > EU_0, UNITS_INDEX matches output of

transducer block

Set values to valid range(s).

CHANNEL

0

1-2

Initial value is a configuration error. Set value to valid range.

SP_RATE_DN

SP_RATE_UP

+INF

0-15

Set value to valid range.

SP_HI_LIM,

100

0-100

Set value to valid range.

SP_LO_LIM

0

0-100

Set value to valid range.

SHED_OPT

0

1-8(seeShedOptionsinthe

FFspecs.)

Initial value is a configuration error. Set value in valid range.

BYPASS

0

1:OFF,2:ON

Initial value is a configuration error. Set value in valid range.

SHED_OPT

0

1-8(seeShedOptionsinthe

FFspecs.)

Initial value is a configuration error. Set value in valid range.

HI_HI_LIMHI_LIM

+INF

+INF

PV_SCALE, +INF Values must be set in rank order

(e.g.LO_LIM > LO_LO_LIM but < HI_LIM etc.)

LO_LIMLO_LO_LIM

-INF

-INF

PV_SCALE,-INF

Values must be set in rank order.

OUT_HI_LIM

OUT_LO_LIM

100

0

OUT_SCALE+/-10%

Verify that OUT_HI_LIM > OUT_LO_LIM.

SP_HI_LIMSP_LO_LIM

100

0

PV_SCALE+/-10%

Verify that SP_HI_LIM > SP_LO_LIM.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13