9

NEEDS_MAINT_SOON

This indicates that the device needs maintenance soon. Diagnostics has indicated something is out of

tolerance or is going to fail, causing the positioner to possibly be operating with reduced functionality

(Transducer block only)

10

FAULT_STATE_SET

Indicates if the fault state has been set (Resource Block only)

11

LOCAL_OVERRIDE

Indicates if the block has gone into Local Override mode (LO)

12

SIMULATE_ACTIVE

The SIMULATE parameter is being used as the input to the AO block. This occurs if the simulate jumper is

set to Y on the electronics board and the ENABLE_DISABLE field of the SIMULATE parameter is set to 2

13

LINK_CONFIG_ERR

Set by the system. Indicates if all the links for the block configurations are available

14

BLOCK_CONFIG_ERR

Invalid parameter value in block. See Clearing Block configuration Errors

15

OTHER

* Depending on the fieldbus interface application, device operating status and parameter values may appear as text messages. The text in the table is typi-

cal of values or messages seen when using the NI-FBUS Configurator

Table 10.6: Transducer Block BLOCK_ERR diagnostics mapping

Diagnostic Flag

BLOCK_ERR Alarm Issued

POSITION_DEVIATION _ALARM

BLK_ERR_DEV_NEEDS_MAIN_NOW

FACTORY_RESET_STATE

BLK_ERR_DEV_NEEDS_MAIN_NOW

STROKE_CAL_REQUIRED

BLK_ERR_DEV_NEEDS_MAIN_NOW

SUPPLY_PRESS_LOW_ALARM

BLK_ERR_DEV_NEEDS_MAIN_NOW

LOSS_INTERBOARD_PCB

BLK_ERR_DEV_NEEDS_MAIN_NOW

MECHANICAL_STATUS not ZERO

BLK_ERR_DEV_NEED_MAINT_SOON

ELECTRONIC_STATUS not ZERO

BLK_ERR_DEV_NEED_MAINT_SOON

SUPPLY_PRESS_HIGH_WARNING

BLK_ERR_DEV_NEED_MAINT_SOON

SUPPLY_PRESS_LOW_WARNING

BLK_ERR_DEV_NEED_MAINT_SOON

PORT_A_VALUE_OUT_OF _RANGE

BLK_ERR_DEV_NEED_MAINT_SOON

PORT_B_VALUE_OUT_OF_RANGE

BLK_ERR_DEV_NEED_MAINT_SOON

PORT_A_RANGE_TOO_SMALL

BLK_ERR_DEV_NEED_MAINT_SOON

PORT _B_RANGE_TOO_SMALL

BLK_ERR_DEV_NEED_MAINT_SOON

PNUEMAITC_LEAK_WARN ING

BLK_ERR_DEV_NEED_MAINT_SOON

SPOOL_STICKING_WARNING

BLK_ERR_DEV_NEED_MAINT_SOON

SPOOL_STICKING_ALARM

BLK_ERR_DEV_NEED_MAINT_SOON

SPOOL_CYCLES_WARNING

BLK_ERR_DEV_NEED_MAINT_SOON

SPOOL_TRAVEL_WARNING

BLK_ERR_DEV_NEED_MAINT_SOON

HALL_SENSOR_UPPER_POSITION

BLK_ERR_DEV_NEED_MAINT_SOON

HALL_SENSOR_LOWER_POSITION

BLK_ERR_DEV_NEED_MAINT_SOON

FEEDBACK_RANGE_TOO_SMALL

BLK_ERR_DEV_NEED_MAINT_SOON

POSITION_OUT_OF_RANGE_LOW

BLK_ERR_DEV_NEED_MAINT_SOON

POSITION_OUT_OF_RANGE_HIGH

BLK_ERR_DEV_NEED_MAINT_SOON

NO_MOTION_TIME_OUT

BLK_ERR_DEV_NEED_MAINT_SOON

NON_SETTLE_TIME_OUT

BLK_ERR_DEV_NEED_MAINT_SOON

INNER_LOOP_OFFSET_TIME_OUT

BLK_ERR_DEV_NEED_MAINT_SOON

JOG_CALIBRATE_SET_100_POS

BLK_ERR_DEV_NEED_MAINT_SOON

10.5 Block Configuration Errors

Configuration Errors

Block configuration errors prevent a device block from leaving OOS mode. The BLOCK_ERR parameter (bit 1) shows whether a block configu-
ration error is present. Table 10.7 summarizes the conditions that may be the result of block configuration errors, which in turn cause a device
fault. Follow the recommended actions to correct these errors.

Logix 3400MD Digital Positioner LGENIM3405-02 11/13