6 tech transducer block – Flowserve 400MD Logix User Manual

Page 39

Advertising
background image

Signatures See Section 10.13, Initiating a Valve Signature for more details on using the signature acquisition functions of the Logix 3400MD digital
positioner.

Custom Characterization See Section 10.11, Stroke Characterization for more details on using the custom characterization features of the Logix 3400MD
digital positioner.

8.6 Tech Transducer Block

The Tech Transducer block contains the parameters used by a technician to troubleshoot a positioner. Many of these parameters are not up-
dated on a regular basis. In order to cause these parameters to update on a regular basis the TEST_MODE parameter in the Main Transducer
block must have the diagnostics enabled.

Section 10.16 Lists the parameters that do not update unless TEST_MODE is selected.

Table 8.7 Tech Transducer Block Parameters

Index

Origin

Name

Store

Date Type

Default Value

0STND XDTB_TECH

SRW Record

BLOCK

0

1STND ST_REV

SR

Simple

UNSIGNED16

1

2STND TAG_DESC

SRW Simple

OCTET_STRING

“7 “

3STND STRATEGY

SRW Simple

UNSIGNED16

2

4STND ALERT_KEY

SRW Simple

UNSIGNED8

4

5STND MODE_BLK

SRW Record

MODE

0x01;0x01;0x11;0x10

6STND BLOCK_ERR

R

Simple

BIT_STRING

0

7STND UPDATE_EVT

RW Record

ALARM_EVENT

0;0;0,0;0;0;0;0

8STND BLOCK_ALM

RW Record

ALARM_DISC

0;0;0,0;0;0;0;0;0;0

9STND TRANSDUCER_DIRECTORY

NR

Array

UNSIGNED16

0

10STND TRANSDUCER_TYPE

NR

Simple

UNSIGNED16

106

11STND XD_ERROR

R

Simple

UNSIGNED8

0

12STND COLLECTION_DIRECTORY

NR

Array

UNSIGNED32

0

13MFG

ELECTRONIC_STATUS

R

Simple

BIT_STRING

0

14MFG

ELECTRONIC_MASKING

NRW Simple

BIT_STRING

0

15MFG

INNERLOOP_STATUS

R

Simple

BIT_STRING

0

16MFG

INNERLOOP_MASKING

NRW Simple

BIT_STRING

0

17MFG

OUTERLOOP_STATUS

R

Simple

BIT_STRING

0

18MFG

OUTERLOOP_MASKING

NRW Simple

BIT_STRING

0

19MFG

CONFIGURATION_STATUS

R

Simple

BIT_STRING

0

20MFG

CONFIGURATION_MASKING

NRW Simple

BIT_STRING

0

21MFG

PRESSURE_STATUS

R

Simple

BIT_STRING

0

22MFG

PRESSURE_MASKING

NRW Simple

BIT_STRING

0

23MFG

DEVIATION_EFFORT

R

Simple

FLOATING_POINT

0

24MFG

PRESS_CTRL_EFFORT

R

Simple

FLOATING_POINT

0

25MFG

INTEGRAL_EFFORT

R

Simple

FLOATING_POINT

0

26MFG

SPOOL_OFFSET

RW Simple

FLOATING_POINT

0

27MFG

SPOOL_COMMAND

RW Simple

FLOATING_POINT

0

28MFG

BACKOFF_EFFORT

R

Simple

FLOATING_POINT

0

29MFG

SPOOL_POSITION

R

Simple

FLOATING_POINT

0

30MFG

SPOOL_EFFORT

R

Simple

FLOATING_POINT

0

31MFG

PIEZO_OFFSET

R

Simple

FLOATING_POINT

0

32MFG

PIEZO_COMMAND

R

Simple

FLOATING_POINT

0

33MFG

USER_INTERFACE_INSTANT

R

Simple

BIT_STRING

0

34MFG

USER_INTERFACE_ACTIVE

RW Simple

BIT_STRING

0

35MFG

P_GAIN_EFFECTIVE

R

Simple

FLOATING_POINT

0

36MFG

P_GAIN_MULT

SRW Simple

FLOATING_POINT

0.05

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

39

Advertising