MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

14

2.3.2 Modbus Function Codes

The controlling device (master) must conform to the Modbus protocol as defined in the Modbus-IDA Modbus
Application Protocol Specification V1.1a (http://www.Modbus-IDA.org) and support Modbus function codes 01
through 06, 08, 15, and 16. These function codes are a subset of the complete protocol and are defined in Table 2.1.

Table 2.1 – Modbus function codes supported

Extended

Function

Bit/Register

Addressing

Code

Name

Addressing

Range

01

Read Coil Status

Bit

0,000 - 9,999

02

Read Discrete Inputs

Bit

10.000 - 19,999

03

Read Holding Register

Register

40,000 - 49,999

04

Read Input Register

Register

30,000 - 39,999

05

Force Single Coil

Bit

0,000 - 9,999

06

Preset Single Register

Register

40,000 - 49,999

08

Diagnostics

N/A

N/A

15

Force Multiple Coils

Bit

0,000 - 9,999

16

Preset Multiple Registers

Register

40,000 - 49,999

See Table 2.2 for a complete listing of MX/DDC holding registers.

2.3.3 Modbus Function Code 01 (Read Coil Status)

This function code is used to read the coil status in the DDC-100 Field Unit. There are nine coils available to be read
on DDC-100 Field Units as shown in Table 2.2. For the MX/DDC, Coil 1 indicates CLOSE contactor and is interlocked
with Coil 2, Coil 2 indicates OPEN contactor and is interlocked with Coil 1. When the I/O Module is used in non-MOV
(motor-operated valve) mode, relays 1 through 6 or coils 3 through 8 are available for user configuration.

Table 2.2 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs

Coil Number

Bit Number

Function

1

00

Close/Stop

2

01

Open/Stop

3

02

S1 or R1 (Opt) Latched

4

03

S2 or R2 (Opt) Latched

5

04

R3 (Opt) Latched

6

05

R4 (Opt) Latched

7

06

R5 (Opt) Latched

8

07

R6 (Opt) Latched

9

08

R7 (Opt) Latched

10

09

R8 (Opt) Latched

The normal response to the (05) command is an echo of the command.

Example
Poll field unit number 3 for 8 coils starting at coil 1.

Query: 0301000000083C2E

Response: 03010118503A