MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

flowserve.com

Message Breakdown

Query

Response

03

Slave (Field Unit) Address

03

Slave (Field Unit) Address

08

Function

08

Function

00

Subfunction Hi

00

Subfunction Hi

00

Subfunction Lo

00

Subfunction Lo

00

Data Hi

00

Data Hi

00

Data Lo

00

Data Lo

E1E9

Error Check (CRC)

E1E9

Error Check (CRC)

Table 2.7 – Diagnostic Codes Supported by the DDC-100 Field Unit

Code

Name

00

Return Query Data

01

Restart Communication Option

02

Return Diagnostic Register

1

03

Change ASCII Input Delimiter

04

Force Listen-Only Mode

10 (0A Hex)

Clear Counters and Diagnostics Register

11 (0B Hex)

Return Bus Message Count

12 (0C Hex)

Return Bus Communication Error Count

13 (0D Hex)

Return Bus Exception Error Count

14 (0E Hex)

Return Slave Message Count

Note 1: Contains DDC-100 Field Unit diagnostic information. For engineering use only.

2.3.10 Modbus Function Code 15 (Force Multiple Coils)

This function code allows the user to force multiple coils with a single command and uses the same coil assignments
as the function code 05.

It should be noted that the coils are operated from the lowest coil number to the highest. Forcing coil 1 or 2 OFF (0) is
considered a stop command, sending a 15 command to force two coils starting with coil 1, with coil 1 ON and coil 2
OFF, would result in the unit stopping, since coil 2 is forced OFF after coil 1 is forced ON.

To prevent inadvertent Stop commands from being issued, it is recommended to force one coil at a time.

Available digital outputs for DDC-100 Field Units are listed in Table 2.5. Force multiple coil commands should be
issued only once for the desired field unit control. Repeated issuance of an acknowledged command will degrade
network performance.

NOTE: This function code is implemented in UEC-3-DDC Modbus Firmware 2.00 and greater and MX-DDC Firmware
02/01.00 and greater

Example of force coil command
Force coil 1 of field unit 1 ON. This will CLOSE the valve controlled by field unit 1.

Query: 010F000000010101EF57

Response: 010F00000001940B