Flowserve MX-100 Field Unit User Manual

Page 16

Advertising
background image

MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

16

Table 2.3 – Status Bit Definitions (continued)

Bit Number

Modbus

Bit

Address

MX/DDC

157

156

Field unit microprocessor has reset since the last poll

158

157

MX in stop move

159

158

Opening in local mode

160

159

Closing in local mode

161

160

Close contactor (interlocked)

162

161

Open contactor (interlocked)

163

162

S1 or R1 (opt)

164

163

S2 or R2 (opt)

165

164

R3 (opt)

166

165

R4 (opt)

167

166

R5 (opt)

168

167

R6 (opt)

169

168

R7 (opt)

170

169

Network relay

171

170

R8 (opt)

172

171

Not used

173-176

172-175

Mov series (0=1, A=9)

177

176

Remote switch

178

177

Thermal overload

179

178

Open torque switch

180

179

Open limit switch

181

180

Close torque switch

182

181

Close limit switch

183

182

Not used

184

183

Not used

185

184

User Input 0

186

185

User Input 1

187

186

User Input 2

188

187

Remote stop input

189

188

Remote open input

190

189

Remote close input

191

190

Not used

192

191

Not used

193

192

Analog board 1 present

194

193

Analog board 2 present

195

194

Analog Input #1 lost

196

195

Analog Input #2 lost

197

196

Network Channels A/B timed out

198

197

Relay board R5-R8 present

199

198

DDC board present

200

199

Relay board R1-R4 and RM present

201

200

FF board present

202

201

PB PA board present

203

202

CLE assigned for input 2

204

203

DNET board present