MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

42

1. “CHANGE MODUTRONIC?
2. Select “YES.”
3. “STATUS (ON) – OK?”
4. Select “YES.”
5. “PROP BAND (15%) – OK?
6. Select “NO” until desired position is viewed. Then select “YES.”
7. “FAIL POSITION (CLOSE) – OK?
8. Select “NO” until desired position is viewed. Then select “YES.” (This setting will have no meaning with DDC.)
9. “DEADBAND (2%) – OK?
10. Select “NO” until desired value is viewed. Then select “YES.”
11. “POLARITY 20MA=OPEN – OK?
12. Select “YES.”
13. “DELAY AFTER STOP 0 SECONDS – OK?
14. Select “YES.”
15. “4-20MA SIGNAL RANGE?
16. Select “NO.”
17. “CHANGE MODUTRONIC?
18. Select “YES.”
19. “STATUS (ON) – OK?
20. Select “NO.”
21. “STATUS (OFF) – OK?
22. Select “YES.”
23. Exit SETUP.
NOTE: Modutronic STATUS must be OFF, once the proportional band and deadband values are changed.

Table 3.4 – MX/DDC digital input configurations (only one selection per row is permitted)

Digital Input Default

Digital Input

Digital Input Options

ESD

User Input 0

Open/Close Inhibit, Both Inhibits,

User Defined

Open Inhibit

User Input 1

Open/Close Inhibit, Both Inhibits,

User Defined

Close Inhibit

User Input 2

Open/Close Inhibit, Both Inhibits,

User Defined, CSE Remote

Three-Wire Inching

User Input 3,4,5

Three-Wire Maintained, Four Wire

Table 3.5 – MX/DDC digital inputs (cross-reference of various inputs)

Terminal #

Basic Function

Digital Input

True Value

1

False Value

Register . Bit

30

ESD Input (default)

User Input 0

1

0

12 . 08

34

Open Inhibit (default)

User Input 1

1

0

12 . 09

35

Close Inhibit (default)

User Input 2

1

0

12 . 10

26

Stop PB Input

User Input 3

0

1

12 . 11

25

Open PB Input

User Input 4

1

0

12 . 12

27

Close PB Input

User Input 5

1

0

12 . 13

Note 1: True value indicates voltage present at terminal point.