MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

52

Appendix – Wiring Diagram

Figure A.1 (1 of 2) – Typical MX/DDC-100 wiring diagram

NOTE: (SEE INSTALLATION & OPERATION MANUAL FOR DETAILS – LMENIM2306)

TYPE TAPS

APPL. VOLTAGES

TYPE TAPS

APPL. VOLTAGES

TYPE TAPS

APPL. VOLTAGES

1

106 V

110 V

2

226 V

226 V, 260 V, 240 V

3

212 V

220 V

115 V

115 V, 120 V

366 V

380 V

505 V

525 V

200 V

208 V

392 V

400 V, 415 V

530 V

550 V

220 V

220 V

450 V

440 V, 460 V, 480 V

572 V

575 V, 600 V

8. EXACT END POSITION INDICATION

REVERSING

CONTACTOR

CLOSE

STOP

OPEN

DIG COM #2-Ve

AUXILIARY INPUT

SEE NOTE 2 &10

0 VAC

110 VAC

24 VDC +Ve

0 VDC

24 VDC +Ve

0 VDC

27

26

25

35

28

29

34

24

21

22

7

6

L1

L2

L3

FS1

FS2

LIMIGARD

45

48

49

46

47

50

51

S1a

S1b

S2a

S2b

"CLOSE"

POSITION

"OPEN"

POSITION

54

53

52

SHOWN

WITH

POWER

SUPPLY

OFF

CONTROL PANEL

MOTOR

1. FUSES

FSI (PRIMARY)

FS2 (PRIMARY)

3. MAXIMUM EXTERNAL LOAD

TERMINALS 21 AND 22 (24 VDC) - 5 W MAX. EXT. LOAD
TERMINALS 23 AND 24 (OPT. 110 VAC) - 20 W MAX EXT. LOAD, 15 VA

REQUIRED CONTROL SIGNAL DURATION = 350 ms MIN.

6. STATUS FEEDBACK OUTPUT SWITCHES

THE ACTUATOR STATUS CONTACTS (S1 & S2) MAY

BE INDIVIDUALLY CONFIGURED AS NORMALLY

OR AS BLINKER CONTACTS, TO INDICATE
ONE OF THE FUNCTIONS LISTED BELOW:
CLOSE
CLOSING
MID-TRAVEL
OPENING
OPEN
STOPPED

9. DEFAULT [S] SETTING

THE DEFAULT OPERATING CONFIGURATION FOR THE
"S" OUTPUTS ARE SHOWN IN THE TABLE BELOW.
THE CONTACT STATES SHOWN IN THE SCHEMATIC
REPRESENT A FULLY CLOSED VALVE.

PE

3 PHASE
SUPPLY

7. CONTACT RATINGS

TOR

QUE

SENSOR

POSITION

SENSOR

MONITOR RELAY

VALVE MOVING

VALVE JAMMED
MOTOR OVERTEMP
OVERTORQUE

CLOSE TORQUE SW

OPEN TORQUE SW

CLOSE INHIBIT
OPEN INHIBIT

ESD SIGNAL
ANALOG IP LOST
LOST PHASE
LIMIGARD ACTIVE
HARDWARE FAILURE

CONTROL

SUPPLY

OPEN OR NORMALLY CLOSED LATCHED CONTACTS,

LOCAL SELECTED

LOCAL STOP/OFF
MANUAL OVERRIDE

REMOTE SELECTED

OUTPUT SWITCH CONTACT DEVELOPMENT

VALVE POSITION

FULL

CLOSE

FULL

OPEN

FUNCTION

CLOSE LIMIT

S2b

OPEN LIMIT

S2a

S1a
S1b

OUTPUT

SWITCH

BACK-UP 24 VDC UPS POWER MAY BE CONNECTED
TO TERMINALS 6 AND 7. MAXIMUM CURRENT
DRAW IS 1 AMP. THIS POWERS ALL CONTROLS FOR

REVERSING CONTACTOR WILL NOT BE POWERED.

CUSTOMER MUST SUPPLY EXTERNAL FUSE AS REQUIRED

ON TORQUE-SEATED VALVES THE LCD AND "S"
CONTACTS, CONFIGURED AS END OF TRAVEL LIMITS,
AUTOMATICALLY PROVIDE EXACT END OF POSITION
INDICATION.

2. AUXILIARY INPUT

600 VAC, 1 A, 200 kA Int RATING,
FAST ACTING 10.3 x 38.1 mm TUBE.

FS3 (SECONDARY) - 0.1 A, 250 V, TIME DELAY,
5 x 20 mm, GLASS TUBE

S1, S2 - 0.5 A @ 125 VAC, 2 A @ 30 VDC

MONITOR - 0.5 A @ 125 VAC, 2 A @ 30 VDC

STATUS FEEDBACK

OUTPUT SWITCHES

SEE NOTES 6,7,8 & 9

DEFAULT SETTING

32

30

DIG COM #1-Ve

DIG COM #3-Ve

2 mA / 24 VDC

MAX LOAD - 10 mA / 110 VAC

MAXIMUM "OFF" 5.0 VAC/VDC

SIGNAL THRESHOLD - MINIMUM "ON" 19.2 VAC/VDC

4. REMOTE INPUTS

INPUT 2

INPUT 1

INPUT 0

44

23

CSE CONTROL

DIG COM #2A

31

DIG COM #3A

33

}

OPT.

(OPTIONAL)

JUMPERS ARE USER WIRED TO CONNECT DIG COMMONS
#1, 2 & 3 (AS NEEDED).

(OPTIONAL W/ BACKUP POWER BOARD)

(RESISTIVE)

(RESISTIVE)

5. REMOTE INPUT JUMPERS

SEE

NOTE 5

SEE TABLE 1

S1a & S1b HAVE COMPLEMENTARY LOGIC

S2a & S2b HAVE COMPLEMENTARY LOGIC

LEGEND
OPEN CONTACT
CLOSED CONTACT

BY LOCAL ELECTRICAL CODES.

GR

OUP 1

GR

OUP 2

GR

OUP 3

REMOTE

INPUTS

SEE NOTE 4

SEE TABLE 1

FS3

(OPTIONAL)

LOCAL INDICATION AND CONFIGURATION.

NETWORK CONTROLLED

INPUTS 0,1,2 ARE FIELD CONFIGURABLE FOR
CLOSE/OPEN INHIBIT,
REDUNDANT OPEN, CLOSE, STOP [LIMIGARD]
USER INPUT, OR ESD.
IN ADDITION,
INPUT 0 MAY BE CONFIGURED FOR CLOSE;
INPUT 1 MAY BE CONFIGURED FOR STOP;
INPUT 2 MAY BE CONFIGURED FOR CSE
REMOTE SELETION INDICATION:
DEFAULT INPUT CONFIGURATION:
INPUT 0 - ESD,
INPUT 1 - OPEN INHIBIT,
INPUT 2 - CLOSE INHIBIT

DIGITAL OUTPUTS
THE DIGITAL OUTPUTS (S) MAY BE INDIVIDUALLY CONFIGURED AS OPEN
OR CLOSE LATCHED, OR AS BLINKER CONTACTS. S1a, S1b, S2a, S2b,
MAY ALSO BE “DDC CONTROLLED” FROM MASTER STATION.

14

13

3

4

5

NETWORK DATA-A2

NETWORK DATA-A2*

NETWORK DATA-A1

NETWORK DATA-A1*

DDC BOARD

EARTH/GROUND

SURGE PROTECTION

A

REG 9.0x0400

REG 9.0x0800

B

A