MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

24

Table 2.6 – Modbus 06 command and field unit holding register 40001

Host Commands to Field Unit Register 1

Value (Decimal)

Function

Null Command

0

No action

Open

256

Open actuator

Stop

512

Stop actuator

Close

768

Close actuator

Reset Field Unit

1024

Reset processor

Start Network ESD

1280

ESD initiate

Stop Network ESD

1536

ESD terminate

Engage Relay #1

2304

S1 or R1 (opt)

Engage Relay #2

2560

S2 or R2 (opt)

Engage Relay #3

2816

R3 (opt)

Engage Relay #4

3072

R4 (opt)

Engage Relay #5

3328

R5 (opt)

Engage Relay #6

3584

R6 (opt)

Engage Relay #7

3840

R7 (opt)

Disengage Relay #1

4352

S1 or R1 (opt)

Disengage Relay #2

4608

S2 or R2 (opt)

Disengage Relay #3

4864

R3 (opt)

Disengage Relay #4

5120

R4 (opt)

Disengage Relay #5

5376

R5 (opt)

Disengage Relay #6

5632

R6 (opt)

Disengage Relay #7

5888

R7 (opt)

Move-To (Enable)

1

6656

Initiates “move-to”

Engage Relay #8

6912

R8 (opt)

Disengage Relay #8

7168

R8 (opt)

Note 1: This is a two-step command. A valid value must be written to Register 2 before issuing this command.

(See Note 1 of Table 2.2.)

Other registers may also be preset to control or change other functions but care must always be taken to properly
change these values. An improper value written to a register can cause undesirable actions from the DDC-100 Field
Unit.

NOTE: Null Command–The field unit takes no action when this command is received. This command is typically used
by a Host to reset the Host output register when required.

Example of Field Unit Command
Write the command to open an actuator (actuator open) to field unit number 179. This corresponds to writing the
value 256 into field unit register 40001.

Query: B306000001009388

Response: B306000001009388

Message Breakdown

Query

Response

B3

Slave (Field Unit) Address

B3

Slave (Field Unit)

Address

06

Function

06

Function

00

Register Address Hi

00

Register Address Hi

00

1

Register Address Lo

00

Register Address Lo

01

Force Data Hi

01

Preset Data Hi

00

2

Force Data Lo

00

Preset Data Lo

9388

Error Check (CRC)

9388

Error Check (CRC)

Note 1: 0000h equals Register Address 40001 (field unit register 1, command register).

Note 2: 0100h requests the register to be preset with 256 Decimal (engage open contactor).