22

Message Breakdown

Query

Response

46

Slave (Field Unit) Address

46

Slave (Field Unit) Address

04

Function

04

Function

00

Starting Address Hi

08

Byte Count

04

Starting Address Lo

FF

Data Hi (Register 40005)

00

No. of Points Hi

FF

1

Data Lo (Register 40005)

04

No. of Points Lo

FF

Data Hi (Register 40006)

BF7F

Error Check (CRC)

FF

2

Data Lo (Register 40006)

00

Data Hi (Register 40007)

2B

3

Data Lo (Register 40007)

00

Data Hi (Register 40008)

1E

4

Data Lo (Register 40008)

DBA8

Error Check (CRC)

Note 1: FFFFh equals 65535 Decimal (actuator Analog Input 4 value).
Note 2: FFFFh equals 65535 Decimal (actuator Analog Input 3 value).
Note 3: 002Bh equals 43 Decimal (actuator Analog Input 2 value).
Note 4: 001Eh equals 30 Decimal (actuator Analog Input 1 in percent format).

2.3.7 Modbus Function Code 05 (Force Single Coil)

This function code is used to force a single coil in the DDC-100 Field Unit. Forcing the individual coil either ON (1) or
OFF (0) will energize or de-energize a coil (digital output) in the field unit. Coil 1 in the field unit closes the actuator
and Coil 2 opens the actuator. If the actuator is opening or closing, changing the status of coil 1 or 2 from a value of
1 to 0 will stop the actuator (the coil will automatically be set to zero when the actuator reaches the full open or full
close position).

Available digital outputs for DDC-100 Field Units are listed in Table 2.5. Force-coil commands should be issued
only once for the desired field unit control. Repeated issuance of an acknowledged command will degrade network
performance.

NOTE: See Bulletin LMAIM1329, Accutronix Installation and Operation for MX-DDC Field Unit to configure AS and
AR Relays for DDC control.

Table 2.5 – DDC-100 coil assignments, Modbus 05 command usage for digital outputs

Coil Number

Bit Number

Function

1

00

Close/Stop

2

01

Open/Stop

3

02

S1 or R1 (Opt) Latched

4

03

S2 or R2 (Opt) Latched

5

04

R3 (Opt) Latched

6

05

R4 (Opt) Latched

7

06

R5 (Opt) Latched

8

07

R6 (Opt) Latched

9

08

R7 (Opt) Latched

10

09

R8 (Opt) Latched

The normal response to the (05) command is an echo of the command.