4 modbus function code 02 (read input status) – Flowserve MX-100 Field Unit User Manual

Page 15

Advertising
background image

15

MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

flowserve.com

Message Breakdown

Query

Response

03

Slave (Field Unit) Address

03

Slave (Field Unit) Address

01

Function

01

Function

00

Starting Address Hi

01

Byte Count

00

Starting Address Lo

18

1

Data (Coils 8 - 1)

00

No. of Points Hi

503A

Error Check (CRC)

08

No. of Points Lo

3C2E

Error Check (CRC)

Note 1: 18h equals 00011000 or coils 4 and 5 are ON.

2.3.4 Modbus Function Code 02 (Read Input Status)

This function code is used to read the discrete input status bits in the DDC-100 Field Unit. The use of this function
code will provide the user with the input status bits that are used to develop holding registers 9 through 13. The
status bit inputs are contained in locations 10129-10208 for each DDC-100 Field Unit and are defined in Table 2.3.

Table 2.3 – Status Bit Definitions

Bit Number

Modbus

Bit

Address

MX/DDC

129

128

Opened

130

129

Closed

131

130

Stopped in mid-travel

132

131

Opening

133

132

Closing

134

133

Valve jammed

135

134

Not in remote

136

135

Combined fault

137

136

Over-temperature fault

138

137

Actuator failing to de-energize

139

138

Channel A fault

140

139

Channel B fault

141

140

Open torque switch fault

142

141

Close torque switch fault

143

142

Valve operated manually fault

144

143

Phase error

145

144

Open inhibit active

146

145

Close inhibit active

147

146

Not used

148

147

Not used

149

148

One or more phases is missing

150

149

Reverse phase sequence is occurring

151

150

ESD conflict

152

151

Inhibit conflict

153

152

Use in local/stop (input must be set for CSE and enabled)

154

153

Not used

155

154

Network emergency shutdown (ESD) is active

156

155

Local emergency shutdown is active

Advertising