4 user knowledge, 5 ddc-100 system capabilities and features – Flowserve MX-100 Field Unit User Manual

Page 6

Advertising
background image

MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

6

1.4 User Knowledge

It is recommended that the user read this manual in its entirety before the DDC-100 equipped actuator is installed and
operated.

The user needs to have a fundamental knowledge of electronics and microprocessor concepts. An understanding of
valve actuators and digital control systems is beneficial to the field unit user.

1.5 DDC-100 System Capabilities and Features

Limitorque’s distributed digital control (DDC) valve control network supports up to 250 actuators over a single
twisted-pair cable using Modbus™ protocol. MX actuators and other devices can be accessed from a control room
for integration with a plant asset management (PAM) system, distributed control system (DCS), programmable
logic controller (PLC), or personal computer (PC) based network. The DDC-100 system consists of a host system,
controller, network, and field units. A typical DDC-100 system is shown in Figure 1.1.

Figure 1.1 – Typical DDC-100 system with or without a Master Station II

1

2

3

4

5

250

...

Host controller

Optional

Master

Station

Network

RS-485

MX field

units

(up to 250)

Advertising
This manual is related to the following products: