Flowserve MX-100 Field Unit User Manual

Page 19

Advertising
background image

19

MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11

flowserve.com

Table 2.4 – Register definitions (continued)

Register #

Description

Meaning

10

Fault Register

16 Bits of field status

Bit 0 Open inhibit active

Bit 1 Close inhibit active

Bit 2 Not Used

Bit 3 Not Used

Bit 4 One or more phases are missing

Bit 5 Reverse phase sequence is occurring

Bit 6 ESD conflict

Bit 7 Inhibit conflict

Bit 8 CSE in local/stop (input must be set for CSE and enabled)

Bit 9 Not Used

Bit 10 Network emergency shutdown is active

Bit 11 Local PB emergency shutdown is active

Bit 12 Field unit microprocessor has reset since the last poll

Bit 13 MX in stop mode

Bit 14 Opening in local mode

Bit 15 Closing in local mode

11

Digital Outputs

Value of 16 Digital Outputs

Bit 0 Close contactor (Interlocked)

Bit 1 Open contactor (Interlocked)

Bit 2 S1 or R1 (Opt)

Bit 3 S2 or R2 (Opt)

Bit 4 R3 (Opt)

Bit 5 R4 (Opt)

Bit 6 R5 (Opt)

Bit 7 R6 (Opt)

Bit 8 R7 (Opt)

Bit 9 Network Relay

Bit 10 R8 (Opt)

Bit 11 Not Used

BIT 12-15 MOV Series (0 = 1, A = 9)

12

Digital Inputs 1

Value of 16 Digital Inputs

Bit 0 Remote Switch

Bit 1 Thermal Overload

Bit 2 Open Torque Switch

Bit 3 Open Limit Switch

Bit 4 Close Torque Switch

Bit 5 Close Limit Switch

Bit 6 Not Used

Bit 7 Not Used

Bit 8 User Input 0 (Default=ESD), Terminal 30

Bit 9 User Input 1 (Default=Open Inhibit), Terminal 34

Bit 10 User Input 2 (Default=Close Inhibit), Terminal 35

Bit 11 Remote Stop Input, Terminal 26

Bit 12 Remote Open Input, Terminal 25

Bit 13 Remote Close Input, Terminal 27

Bits 14-15 Not Used