Horizontal mount, Fig. 3, Fig. 4 fig. 5 – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 11: Vertical mount, In. max. [19mm]) sheet metal screws

Advertising
background image

Horizontal Mount

Damper Model

Maximum Single
Section Size in a

Multiple Section

Assembly

Maximum Over-

all Size for

Multi-Section

Dampers

CFSD-211, 212

24 x 24

NA

DFD-210

32 x 50

128 x 96

DFD-230

32 x 48

72 x 48

DFDAF-310

32 x 50

96 x 50

DFDTF-210

32 x 36

96 x 72

32 x 48

64 x 48 or 32 x 96

FSD-211, 212, 213

36 x 48 or 32 x 50

144 x 96

FSD-211M, 212M

36 x 36

144 x 72

FSD-231

36 x 36 or 32 x 48

72 x 48

FSD-311, 311M, 312,
312M

32 x 50

96 x 50

IMO-310

32 x 50

NA

IMO-311

32 x 50

NA

SEDFD-210,
SEFSD-211

24 x 30

48 x 30

SSFSD-211

24 x 30

48 x 30

FSD-231M

32 x 36

72 x 48

2 in.

Max.

6 in.

Max.

Sleeve

Retaining

Angle

Damper

Duct

Min. 1 in.

Overlap*

Wall or

Floor

Retaining

Angle

*only applicable for damper sizes above 36 in. x 36 in.

6 in.

Max.

2 in.

Max.

Both vertical and horizontal damper installations are typified by these
drawings.

Fig. 3

5. ACTUATOR CONNECTIONS

Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).

6. INSTALLING MULTIPLE DAMPER SECTION

ASSEMBLIES

A damper assembly is not restricted to a maximum
number of sections, but must not exceed the section
sizes and overall sizes shown (see chart).

Two section high dampers require reinforcement using a
14 gauge (2mm), 5 in. (127mm) wide mullion as shown in
Fig. 4 below, or two individually sleeved units stacked
vertically, shown below in Fig. 5. When using two
individually sleeved units, the sleeve acts as the mullion,
therefore no mullion is required.

The damper sections must be attached together with
#10 (

3

/

4

in. max. [19mm]) sheet metal screws,

1

/

4

in. (6mm)

diameter nuts and bolts, tack or spot welds, or

3

/

16

in.

(48mm) diameter steel pop rivets. Attachments must be
spaced a maximum of 6 in. (152mm) on centers and a
maximum of 2 in. (51mm) from corners. Attachments must
be made on front face and back face (air entering and air
exiting side) of damper sections.
Note: Dampers ordered for individual installation may
not be installed together. The full assembly size must be
specified at the time the dampers are ordered.

14 ga.
5 in. wide
support
mullion

Fig. 4

Fig. 5

Single Sleeve Around Outside with

Support Mullion

Two Individually Sleeved Units

with No Mullions

NOTE:

FSD model dampers fitted with a fusible link closure

device are limited to single section sizes. Dampers with a
fusible link and spring assembly closure device may not be
used for multiple section applications

.

Vertical Mount

Damper Model

Maximum Single
Section Size in a

Multiple Section

Assembly

Maximum

Overall Size for

Multi-section

Dampers

DFD-210

32 x 50

128 x 100

DFD-230

32 x 50

72 x 48

DFDAF-310

32 x 50

128 x 100

DFDTF-210

32 x 36

96 x 72

32 x 50

64 x 50

FSD-211, 212, 213

36 x 48 or 32 x 50

128 x 100

FSD-211M, 212M

36 x 36

128 x 72

FSD-231

36 x 36 or 32 x 48

72 x 48

FSD-311, 311M,
312, 312M

32 x 50

128 x 100

IMO-311

32 x 50

NA

32 x 50

NA

SEDFD-210,
SSDFD-210

24 x 30 or 22 x 36

48 x 30

SEFSD-211
SSFSD-211

24 x 30 or 22 x 36

88 x 72

FSD-331; DFDAF-330

30 x 48

120 x 96

FSD-231M

32 x 36

72 x 48

11

Advertising