Figure 9: 1 hour wall rating, Figure 10: 2 hour wall rating – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 51

Advertising
background image

Masonry or
Concrete Floor

Damper

Sleeve

Angle Fastener

(see Section 2)

Top Side

Figure 7: Masonry or Concrete Wall

Figure 8: Concrete Floor

Copyright © 2013 Greenheck Corporation

474015 Single Side Retaining Angle Suppl Rev. 3 Jan 2013

Masonry or
Concrete Wall

Damper

Sleeve

Angle Fastener

(see Section 2)

2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont.......

Grille Installations (Dampers up to 36 in. x 36 in.
[914mm x 914mm] maximum)
• Angle legs may be reversed and one leg inserted
into the wall/floor opening. Retaining angles used in
conjunction with grille installations must be a minimum
of 20 gauge (1mm) steel and have a minimum of
5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel.

Space screws a maximum of 6 in. (152mm) on center
and a maximum of 2 in. (51mm) from the corners
(minimum of 2 screws per side). See Figure 9 and
Figure 10.
Note: Screws used to attach grille are allowed to
penetrate reversed angle leg.

Damper

Sleeve

Angle Fastener

(see Note 2)

Grille (supplied

by others)

#10 sheet metal screws

spaced 6 in. on center

and a maximum of 2 in.

from the corners

(minimum of 2 screws per

side). Screw into studs so

as to avoid space

conflicts with the grille

1

/

2

in. UL Classified

Gypsum Wallboard (see

UL Rated Wall Design

for Additional Details)

2

1

/

2

in.

Min.

Stud or Runner

Retaining Angle
(See Section 2)

Figure 9: 1 Hour Wall Rating

Damper

Sleeve

Angle Fastener

(see Note 2)

Grille (supplied

by others)

#10 sheet metal screws

spaced 6 in. on center

and a maximum of 2 in.

from the corners

(minimum of 2 screws per

side). Screw into studs so

as to avoid space

conflicts with the grille

1

/

2

in. UL Classified

Gypsum Wallboard (see

UL Rated Wall Design

for Additional Details)

2

1

/

2

in. Min.

Stud or Runner

Two layers of

Retaining Angle
(See Section 2)

Figure 10: 2 Hour Wall Rating

Note: For horizontal installations, retaining angles must be
mounted on top side of partition.

51