Fig. 17, Fig. 18, Fig. 13 – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 14: Fig. 15, Fig. 16 14

Advertising
background image

Duct

Sleeve

6 in.

Std. Clip

Length

CL

Duct

60 in. Duct

4 Req’d.

48 in. Duct

3 Req’d.

36 in. Duct

3 Req’d.

24 in. Duct

2 Req’d.

18 in. Duct &

Smaller

1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in.

6 in.

9 in.

7 in.

7 in.

5 in.

5 in.

5 in.

5 in.

Fig. 17

Duct End
Flange

Corner Piece

3/8 in. bolt
(optional)

Fig. 18

9. DUCT-SLEEVE CONNECTIONS
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.

• The breakaway connections shown (Fig. 14) can be

applied with maximum of two #10 (19mm) sheet metal
screws on each side and on the bottom located in the
center of the slip pocket and penetrating both sides of
the slip pocket.

• Transverse joints illustrated

can be applied as top and
bottom joints with Drive Slip -
side joints in duct heights up
to 20 inches (508mm)
See Fig. 13.

Drive Slip Joint

Fig. 13

Plain “S” Slip Hemmed “S” Slip

Double “S” Slip

Inside Slip Joint

Standing “S”

Standing “S” (Alt.)

Standing “S” (Alt.)

Standing “S”

Standing “S”

(Bar Reinforced)

(Angle Reinforced)

Fig. 14

Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:

• Ducts to 22 in. (558mm) wide (or dia.) and smaller

shall have three screws.

• Ducts larger than 22 in. (558mm) wide (or dia.) up to

and including 36 in. (914mm) wide (or dia.) shall have
five screws.

NOTE: All breakaway connections described may have duct

sealant applied, PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal

®

,

or CL Ward S Seal in accordance with

SMACNA recommendations.

Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by Ductmate,
Durodyne, Ward, and Nexus are approved as breakaway
connections when installed as illustrated (Fig. 15).

Fire Damper Sleeve

Neoprene or Butyl gasket

between all angles

Flanged system angles

(Attach per

manufacturer's

instructions)

Duct

3/8 in. bolts in
corners are optional

6 in. long 1/16 in. max.

thickness plastic cleats;

12 in. c-c (min. 1 per side)

Fig. 15

Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway
connections when installed as described in the TDC or
TDF addendum to the SMACNA
Duct Construction. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in diagram
(see Fig. 15 & 16). 3/8 in. (9.5mm)
metal bolts and nuts may be used
to fasten together corner pieces.
(see Fig. 17)

Duct

Sleeve

6 in.

Std. Clip

Length

CL

Duct

60 in. Duct

4 Req’d.

48 in. Duct

3 Req’d.

36 in. Duct

3 Req’d.

24 in. Duct

2 Req’d.

18 in. Duct &

Smaller

1 Req’d.

Clip Spacing

Typical TDC/TDF joint

6 in.

6 in.

9 in.

7 in.

7 in.

5 in.

5 in.

5 in.

5 in.

Fig. 16