Breakaway connections, Traditional breakaway style transverse joints, Proprietary flange system breakaway connections – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 5: Manufactured flanged system breakaway connections, Round and oval duct breakaway connections, Fig. 6, Fig. 7, Fig. 8, Fig. 5, Fig. 3

Advertising
background image

Traditional Breakaway Style Transverse

Joints

Transverse joints illustrated at right have always
been approved as breakaway connections. SMACNA
testing has also approved the following variations as
breakaway connections.

• The breakaway connections shown below (Fig. 3)

can be applied with maximum of (2) #10 sheet metal
screws on each side and on the bottom located in
the center of the slip pocket and penetrating both
sides of the slip pocket.

• Transverse joints illustrated can be applied as top

and bottom joints with Drive Slip - side joints in
duct heights up to 20 inches (508mm). See Fig. 4.

Proprietary Flange System Breakaway

Connections

(TDC by Lockformer, TDF by Engle)
TDC and TDF systems (see Fig.
6) are approved as breakaway
connections when installed as
described in the TDC or TDF
addendum to the SMACNA Duct
Construction Standards except
the corners may not be bolted.
Standard 6 in. (152mm) metal clip
may be used with spacing as shown in diagram (see
Fig. 7). 3/8 in. (9.5mm) metal bolts and nuts may be
used to fasten together corner pieces together (see
Fig. 8).

Duct

Sleeve

6

9

7

7

5

5

5

5

6

Std. Clip

Length

CL

Duct

60 Duct

4 Reqd.

48 Duct

3 Reqd.

36 Duct

3 Reqd.

24 Duct

2 Reqd.

18 Duct &

Smaller

1 Reqd.

Clip Spacing

Typical TDC/TDF

joint

6

Fig. 6

Duct

Sleeve

6

9

7

7

5

5

5

5

6

Std. Clip

Length

CL

Duct

60 Duct

4 Reqd.

48 Duct

3 Reqd.

36 Duct

3 Reqd.

24 Duct

2 Reqd.

18 Duct &

Smaller

1 Reqd.

Clip Spacing

Typical TDC/TDF

joint

6

Fig. 7

Duct End
Flange

Corner Piece

3/8 in. bolt
(optional)

Fig. 8

Fire Damper Sleeve

Neoprene or Butyl gasket

between all angles

Flanged system angles

(Attach per

manufacturer's

instructions)

Duct

3/8 in. bolts in
corners are optional

6 in. long 1/16 in. max.

thickness plastic cleats;

12 in. c-c (min. 1 per side)

Manufactured Flanged System Breakaway

Connections

Flanged connection systems manufactured by
Ductmate, DuroDyne, Ward, and Nexus are approved
as breakaway connections when installed as illustrated.

Fig. 5

Round and Oval Duct Breakaway

Connections

Round or flat oval ducts connected to Type R, CR or
CO damper collars may use no. 10 sheet metal screws
as follows:

• Ducts to 22 in. (559mm) wide (or dia.) and smaller

may use 3 screws.

• Ducts larger than 22 in. (559mm) wide (or dia.) may

use 5 screws.

NOTE: All breakaway connections described may have
duct sealant applied, PA2084T Duct Sealant Adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey
Pookie, Ductmate PROseal® or CL Ward S Seal in
accordance with SMACNA recommendations.

Plain “S” Slip Hemmed “S” Slip

Double “S” Slip

Inside Slip Joint

Standing “S”

Standing “S” (Alt.)

Standing “S” (Alt.)

Standing “S”

Standing “S”

(Bar Reinforced)

(Angle Reinforced)

Fig. 3

BREAKAWAY CONNECTIONS

Drive Slip Joint

Fig. 4

5