Fig. 2, Fig. 3 – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 31

Advertising
background image

Sleeve Gauge

Duct Dimension

Type of Duct

to Sleeve

Connection

Permitted

14 ga. (0.075 in.)

- 10 ga. (0.138

in.)

[2mm - 3.5mm]

All duct sizes

Rigid or

Breakaway

16 ga. (0.060 in.)

[1.5mm]

36 in. (914mm) max. width
24 in. (610mm) max. width

24 in. (610mm) diameter

Rigid only

16 ga. (0.060 in.)

[1.5mm]

All duct sizes

Breakaway only

18 ga. (0.048 in.)

[1.2mm]

85 in. (2159mm) wide and

over

20 ga. (0.036 in.)

[0.9mm]

55 in. - 84 in. wide

(1397mm - 2134mm)

22 ga. (.030 in.)

[0.76mm]

31 in. - 54 in. wide

(787mm - 1372mm)

24 ga. (0.024)

[0.6mm]

13 in. - 30 in. wide
(330mm - 762mm)

26 ga. (0.018 in.)

[0.46mm]

12 in. wide and under

(305mm)

See page 6 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.

4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO

WALL OPENINGS

Damper/sleeve assemblies must be installed in wall
openings using retaining angles on at least one side of
the wall as described below:
• Retaining angles for 11/2 hour rated dampers with a

width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3
hour rated dampers and all dampers with a width or
height greater than 48 in. (1219mm) must be a minimum
of 16 gauge (1.5mm). The leg of the retaining angle
on the damper sleeve shall be a minimum of 11/4 in.
(32mm). The leg of the retaining angle on the wall/floor
shall be long enough to cover the annular space and
overlap the wall/floor by a minimum of 1 in. (25mm).

Damper

Model

Maximum Single

Section Size

Maximum Multiple

Section Size

FSD-311V

50 x 32

100 x 32

Type R and O

Factory Furnished

Duct Collars Qualify

As Breakaway

Connections

Duct

Damper

Sleeve

Wall or Floor

Type C, O, R

Fig. 2

Damper with type R or O transition factory

furnished.

2 in. Max.

6 in. Max.

Sleeve

Retaining

Angle

Damper

Duct

Min. 1 in.

Overlap*

Wall or

Floor

Retaining

Angle

*only applicable for damper sizes above 36 in. x 36 in.

6 in. Max.

2 in. Max.

Both vertical and horizontal damper installations are
typified by these drawings.

Fig. 3

5. ACTUATOR CONNECTIONS

Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).

• Retaining angle must be attached to the damper using

one or more of the following methods of attachment
(refer to label on outside of sleeve for ‘No Screw’ area):

• Tack or spot welds
• #10 (

3

/

4

in. max. [19mm]) sheet metal screws

1

/

4

in. (6mm) bolts and nuts

3

/

16

in. (5mm) steel pop rivets

A minimum of two connections per side, top, and bottom,
12 in. (305mm) O.C. (on center) maximum for openings of
48 in. W x 32 in. H (1219mm x 812mm) and less, and 6 in.
(152mm) O.C. for openings 100 in. W x 32 in. H (2540mm
x 32mm) or less. The angles must be attached to all 4
sides of the sleeve with butt joints at each corner. A
minimum of two attachments are required on each side,
top and bottom. Ensure that attachment device does not
interfere with the operation of the damper and the free
movement of the damper blades. The angles need not be
attached to each other at the corners. Do not secure the
retaining angle to the fire separation (see Fig. 3).
• Retaining angles should not be fastened to the wall

material. The angles should only sandwich the wall and
allow for damper expansion during periods of intense
heat.

31

Advertising