Sleeve length and wall/floor thickness, Round duct connections – Greenheck Multi-blade Fire & Combination Fire Smoke Dampers Installation Booklet (826249) User Manual

Page 38

Advertising
background image

3.375 IN.

FUSIBLE
LINK
LOCATION

CLEARANCE FOR
EXPANSION

TOP VIEW OF DAMPER

6 IN. MAX

SLEEVE LENGTH

TW

DUCT
CONNECTION
AREA

AIRFLOW

2.00 IN.

ACTUATOR

16.00 IN MAX

OPTIONAL BLADE POSITION

INDICATOR AND/OR ELECTRIC

LINK.

DUCT
CONNECTION
AREA

2.00 IN.

1.50 IN.

Optional
Second
Retaining
Plate

Do not place retainer
plate in this groove

Fig. 1

2. SLEEVE LENGTH AND WALL/FLOOR

THICKNESS

Insert the damper assembly into the prepared opening,
to appropriate depth (see Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:

1) the operation of the damper actuator is not

impeded and

2) the

CL of the damper blade remains within

the plane of the wall/floor
IMPORTANT SAFETY DANGER! : To avoid
causing death or serious bodily harm to
building occupants, do not insert screws
into the damper frame unless used for duct
connection within 2 in. (51mm) of the frame
end.

The sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor on the actuator side of the
damper and a maximum of 6 in. (152mm) on the
opposite side.

4. SECURING THE DAMPER/SLEEVE ASSEMBLY

TO WALL AND FLOOR OPENINGS

Damper assemblies must be installed in wall/floor
openings using a single retaining plate on either side of
the wall/floor or by using a retaining plate on both sides
of the wall/floor. The use of a second retaining plate is
allowed, but is not necessary. A single retaining plate
is provided with the dampers. A second retaining plate
can be ordered as an option. The outside dimension of
the supplied retainer plate is nominal dia. + 41/2 inches
(114mm).

3. ROUND DUCT CONNECTIONS

Round duct connections to shall be attached with #8 or
#10 sheet metal screws as follows:

• Ducts 22 in. (558mm) dia. and smaller shall have

three screws.

• Ducts larger than 22 in. (558mm) dia. up to and

including 24 in. (610mm) dia. shall have five screws.

NOTE: All connections described may have duct
sealant, PA2084T duct sealant adhesive manufactured
by Precision, DP1010 water base duct sealant
manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal®, or CL Ward S Seal applied in
accordance with SMACNA recommendations.

1. CLEARANCES REQUIRED BETWEEN FIRE

DAMPER SLEEVES AND WALL/FLOOR
OPENINGS

Fire damper assemblies expand during periods of
intense heat. Therefore, it is essential that openings in
walls or floors be larger than the fire damper assembly
to allow for this expansion. The wall/floor opening
must be a minimum of 7/8 in. (22mm) larger than the
outside diameter of the damper. Refer to Section 4 for
additional installation considerations.

38

Advertising