Document Number 461868

FSDR-XXX, SEFSDR-XXX,

AND SSFSDR-XXX MODELS

1

1

2

Hour Fire & Combination Fire

Smoke Dampers

Vertical and Horizontal Mount

SAFETY WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment. To avoid causing death or serious bodily harm
to building occupants, follow all instructions carefully.
Dampers must close completely to preserve the integrity
of the fire smoke separation.

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.

WARRANTY

Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.

Due to continuing research, Greenheck reserves the right to change specifications without notice.

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards (see

complete marking on product)”

UL Standard 555 & 555S (Classification #R13317)

FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model

Dampers are intended for installation in accordance

with combination fire smoke damper requirements

established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal (CSFM)
Fire Listing (3225-0981:0112)
Leakage Listing (3230-0981:0113)

RECEIVING AND HANDLING

Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.

Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).

Installation, Operation and Maintenance Instructions

INSTALLATION SUPPLEMENTS

Refer to the appropriate Greenheck installation
supplements for special requirements:

• Steel Deck Supplement

SAFETY CAUTION!

Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.

Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring.

ELECTRICAL GUIDELINES

All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.

®