9.4 Cable Connection

9.4.1 Requirements

Cable

• Only use copper or aluminum cables.
• AC cables are designed to carry maximum voltages of 1 450 V to ground and an effective

value of 800 V.

• Connect a maximum of 2 DC cables to each fuse input.

Terminal lugs

• Only use tin-plated crimp-type terminal lugs.
• The width of the terminal lugs must exceed the washer diameter (32 mm). This will ensure that

the defined torques are effective over the whole surface.

9.4.2 Cleaning the contact surfaces of terminal lugs and

connection lugs

1. Clean the contact surfaces with a clean cloth and ethanol cleaner.
2. Clean the contact surfaces with the non-woven abrasive included in the delivery until they have

a slight metallic shine. Avoid damage to the coated contact surfaces.

3. Remove metal dust with a clean cloth and ethanol cleaner.
4. Do not touch the contact surfaces again after cleaning.