5 sunny central 800he, Sunny central 800he – SMA SC 500HE-20 Installation User Manual
Page 71
![background image](/files/819043/content/doc071.png)
SMA Solar Technology AG
14 Technical Data
Installation Manual
SCxxxHE-20-IA-IEN111210
71
Ambient conditions
14.5 Sunny Central 800HE
Input values
Output values
Degree of protection*
* As per DIN EN 60529
IP 21
Operating temperature range
–20°C ... +50°C
Humidity
15% … 95%
Fresh air consumption
3 000 m³/h
Maximum altitude above sea level, MSL
2 000 m
MPP voltage range
583 V
DC
… 820 V
DC
Maximum DC voltage*
* Optional 1 100 V
1 000 V
DC
Maximum DC current
1 400 A
DC
Number of DC inputs
9
Nominal AC power at 50°C
800 kVA
Continuous AC power at 25°C
880 kVA
Maximum AC current
1 411 A
AC
Nominal AC current
1 283 A
AC
Nominal AC voltage ± 10%*
* Thin-film PV modules are subject to a natural aging process. This reduces their performance capacity. The Sunny Central
800HE has the option of adjusting the nominal AC voltage and power to the degradation of the PV modules. You will find
further information on this in the inverter user manual.
360 V
AC
Grid frequency
50 Hz / 60 Hz
Power factor cos φ
0.9
overexcited
… 0.9
underexcited
Maximum total harmonic factor
< 3%