3 checking the external voltage supply, Checking the external voltage supply, See section 12.3.3) – SMA SC 500HE-20 Installation User Manual

Page 61

Advertising
background image

SMA Solar Technology AG

12  Commissioning

Installation Manual

SCxxxHE-20-IA-IEN111210

61

12.3.3 Checking the External Voltage Supply

1. Using a rotating-field instrument, measure the rotating magnetic field at the miniature circuit-

breaker of the external voltage supply. To do this, use the measuring points on the miniature
circuit-breaker of the external voltage supply.
☑ The detected rotating magnetic field is right-rotating.
✖ Is the detected rotating magnetic field left-rotating?

2 line conductors are incorrectly connected.
• Swap over the connections of the two of the three line conductors and repeat the

measurement.

2. Measure the AC voltages at the miniature circuit-breaker of the external voltage supply between

the following terminals and record in the Commissioning Report: To do this, use the measuring
points on the miniature circuit-breaker of the external voltage supply.
– L

1

- L

2

– L

1

- L

3

– L

2

- L

3

– L

1

- N

– L

2

- N

– L

3

- N

– L

1

- PE

– L

2

- PE

– L

3

- PE

– N

- PE

☑ The voltage between the line conductors is within the range of 360 V ... 440 V. The voltage

between line conductor and neutral conductor or PE conductor is within the range of
207 V … 243 V. The voltage between PE conductor and neutral conductor is 0 V.