14 technical data, 1 sunny central 500he, Technical data – SMA SC 500HE-20 Installation User Manual
Page 66: Sunny central 500he
14 Technical Data
SMA Solar Technology AG
66
SCxxxHE-20-IA-IEN111210
Installation Manual
14 Technical Data
14.1 Sunny Central 500HE
Input values
Output values
Power consumption
Dimensions and weight
MPP voltage range
430 V
DC
… 820 V
DC
Maximum DC voltage*
* Optional 1 100 V
1 000 V
DC
Maximum DC current
1 250 A
DC
Number of DC inputs
9
Nominal AC power at 50°C
500 kVA
Continuous AC power at 25°C
550 kVA
Maximum AC current
1 176 A
AC
Nominal AC current
1 069 A
AC
Nominal AC voltage ± 10%
270 V
AC
Grid frequency
50 Hz / 60 Hz
Power factor cos φ
0.9
overexcited
… 0.9
underexcited
Maximum total harmonic factor
< 3%
Self-consumption in operation
< 1 500 W
Standby consumption
< 100 W
External auxiliary supply voltage
3 x 230 V, 50 Hz / 60 Hz
Width x height x depth
2 404 mm x 2 093 mm x 937 mm*
* Without anchorage bracket in base, incl. spreader beam, depth incl. all attached components
Weight
1 670 kg