14  Technical Data

SMA Solar Technology AG

70

SCxxxHE-20-IA-IEN111210

Installation Manual

14.4 Sunny Central 760HE

Input values

Output values

Power consumption

Dimensions and weight

Efficiency

MPP voltage range

554 V

DC

… 820 V

DC

Maximum DC voltage*

* Optional 1 100 V

1 000 V

DC

Maximum DC current

1 400 A

DC

Number of DC inputs

9

Nominal AC power at 50°C

760 kVA

Continuous AC power at 25°C

836 kVA

Maximum AC current

1 411 A

AC

Nominal AC current

1 283 A

AC

Nominal AC voltage ± 10%

342 V

AC

Grid frequency

50 Hz / 60 Hz

Power factor cosφ

0.9

overexcited

… 0.9

underexcited

Maximum total harmonic factor

< 3%

Self-consumption in operation

< 1 500 W

Standby consumption

< 100 W

External auxiliary supply voltage

3 x 230 V, 50 Hz / 60 Hz

Width x height x depth

2 404 mm x 2 093 mm x 937 mm*

* Without anchorage bracket in base, incl. spreader beam, depth incl. all attached components

Weight

1 670 kg

Maximum efficiency

98.6%

Euro-eta

98.4%

CEC-eta

98.5%