8 connecting the external quick-stop cabling, Connecting the external quick-stop cabling – SMA SC 500HE-20 Installation User Manual

Page 52

Advertising
background image

10  Cable Connection in the Connection Cabinet

SMA Solar Technology AG

52

SCxxxHE-20-IA-IEN111210

Installation Manual

Required Material:

• Cable with a maximum conductor cross-section of 4 mm²

1. Lead the external voltage supply cable into the connection cabinet (see section 10.3).
2. Connect the cable according to the circuit diagram (see section 10.4.1).
3. Fasten the cable to the cable anchoring rail using a cable tie. This secures the cable from being

pulled off.

10.4.8 Connecting the External Quick-Stop Cabling

The Sunny Central is equipped by default with a quick-stop button. If the external quick-stop function
is required, it can be connected according to the circuit diagram.

1. Lead the external quick-stop cable into the connection cabinet (see section 10.3).
2. Connect the cable according to the circuit diagram (see section 10.4.1).
3. Fasten the cable to the cable anchoring rail using a cable tie. This secures the cable from being

pulled off.

/05*$&

Damage to the Sunny Central caused by faulty installation of the external quick-stop.
If an external quick-stop is installed incorrectly, this may damage the Sunny Central and restrict the
function of the quick-stop.

• When connecting the external quick-stop cabling, it is obligatory to follow the circuit diagram

included in the delivery. The connection is made at the terminals.

• If no external quick-stop is installed, the terminals must be bridged according to the circuit

diagram.

Routing of the quick-stop cable
The cable entry is the floor of the cabinet.

Advertising