3 sunny central 720he, Sunny central 720he – SMA SC 500HE-20 Installation User Manual

Page 68

Advertising
background image

14  Technical Data

SMA Solar Technology AG

68

SCxxxHE-20-IA-IEN111210

Installation Manual

Power consumption

Dimensions and weight

Efficiency

Ambient conditions

14.3 Sunny Central 720HE

Input values

Self-consumption in operation

< 1 500 W

Standby consumption

< 100 W

External auxiliary supply voltage

3 x 230 V, 50 Hz / 60 Hz

Width x height x depth

2 404 mm x 2 093 mm x 937 mm*

* Without anchorage bracket in base, incl. spreader beam, depth incl. all attached components

Weight

1 670 kg

Maximum efficiency

98.7%

Euro-eta

98.5%

CEC-eta

98.5%

Degree of protection*

* As per DIN EN 60529

IP 21

Operating temperature range

–20°C ... +50°C

Humidity

15% … 95%

Fresh air consumption

3 000 m³/h

Maximum altitude above sea level, MSL

2 000 m

MPP voltage range

525 V

DC

… 820 V

DC

Maximum DC voltage*

* Optional 1 100 V

1 000 V

DC

Maximum DC current

1 400 A

DC

Number of DC inputs

9