2 sunny central 630he, Sunny central 630he – SMA SC 500HE-20 Installation User Manual
Page 67
SMA Solar Technology AG
14 Technical Data
Installation Manual
SCxxxHE-20-IA-IEN111210
67
Efficiency
Ambient conditions
14.2 Sunny Central 630HE
Input values
Output values
Maximum efficiency
98.6%
Euro-eta
98.4%
CEC-eta
98.5%
Degree of protection*
* As per DIN EN 60529
IP 21
Operating temperature range
–20°C ... +50°C
Humidity
15% … 95%
Fresh air consumption
3 000 m³/h
Maximum altitude above sea level, MSL
2 000 m
MPP voltage range
500 V
DC
… 820 V
DC
Maximum DC voltage*
* Optional 1 100 V
1 000 V
DC
Maximum DC current
1 350 A
DC
Number of DC inputs
9
Nominal AC power at 50°C
630 kVA
Continuous AC power at 25°C
700 kVA
Maximum AC current
1 283 A
AC
Nominal AC current
1 155 A
AC
Nominal AC voltage ± 10%
315 V
AC
Grid frequency
50 Hz / 60 Hz
Power factor cos φ
0.9
overexcited
… 0.9
underexcited
Maximum total harmonic factor
< 3%