3 minimum clearances, Minimum clearances, Minimum clearance for 1 inverter – SMA SC 500HE-20 Installation User Manual

Page 23

Advertising
background image

SMA Solar Technology AG

6  Preparation for Installation

Installation Manual

SCxxxHE-20-IA-IEN111210

23

6.1.3 Minimum Clearances

Minimum clearance for 1 inverter

Figure 7: Minimum clearances of the inverter

The exhaust air vent is located at the rear of the inverter.
For the optimum operation of the inverter, observe the following points:

• Do not block or close the exhaust air vent.
• Ensure that the station is equipped with a suitable exhaust air vent.
• In order to prevent thermal short circuits in the inverter, ensure that there are exhaust air ducts

in closed rooms.

• The exhaust air vents must be accessible for cleaning at all times.

8"3/*/(

Danger of fire due to overheating of cables.
Differing cable lengths result in excessive heating of the cables.

• All line conductors from the inverter to the transformer must be of the same length.
• The cable length between the connection points must not exceed a maximum of 15 m.

/05*$&

Damage to the inverter and transformer due to discharged air being sucked in.

• Install the plant so that the inverter cannot suck in any exhaust air.

HE

300 mm

220 mm

300 mm

1 200 mm

Advertising