The specifications of the Power Supply Unit are given in the following table.

Item

Specification

AC Power Supply Unit

DC Power Supply Unit

Model

JEPMC-PSA3012-E

JEPMC-PSD3012-E

Abbreviation

PSA-12

PSD-12

Power Supply
Section

Input Voltage

100/200 VAC

24 VDC

Allowable Input Voltage
Range

85 to 132 VAC or 170 to 276 VAC

19.2 to 28.8 VDC

Allowable Frequency
Range

47 to 63 Hz

-

Input Current

4.0 A max. (at rated input/output)

5.0 A max. (at rated input/output)

Inrush Current

25 A, 10 ms max. (fully discharged, 132-VAC
input, rated output)

50 A, 10 ms max. (fully discharged,

28.8-VDC input, rated output)

50 A, 10 ms max. (fully discharged, 276-VAC
input, rated output)

Allowable Momentary
Power Loss Time

20 ms

1 ms

Rated Voltage

5.15 V

Rated Current

12.0 A

Output Current Range

0 to 12.0 A

0.2 to 12.0 A

Constant Voltage
Accuracy

5.15 V ±2% max. (5.05 to 5.25 V)

Status Output

If the Power Supply Unit is mounted on the Main Rack, this output functions as normally closed
contacts that are synchronized with the status of the CPU Unit.

• Normal operation: Circuit closed.
• Error: Circuit open.

Contact Ratings

Connectors

POWER: Power supply connector
RLY OUT: Relay contact connector

Indicators

POWER

Refer to Indicators on page 12

.

Input Conditions

Inrush Current

For Cold Start

50 A within 10 ms (fully discharged status)

275-VAC input, rated output

For Cold Start

(Through rate at input voltage value increase from
10% to 90% is at 10 ms min.)

50 A within 10 ms (fully discharged status)

28.8-VDC input, rated output

Rise Time

60,000 ms max. (The maximum time for the output control signals to maintain the specified timing
when the primary voltage rises linearly.)

Drop Time

60,000 ms max. (The maximum time that the controls, such as the power failure sequence, can be
maintained when the primary voltage drops linearly.)

Leakage Current

276 VAC 61 Hz: 0.5 mA max.

132 VAC 61 Hz: 0.25 mA max.

-

Efficiency

70% minimum (for rated input voltage and
rated load)

65% minimum (for rated input voltage and rated
load)

Input Voltage

Current Capacity

24 VDC

0.5 A (resistive load)

0.25 A (inductive load)

125 VAC

0.4 A (resistive load)

0.2 A (inductive load)