11 LED Indicators

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

29

11

LED Indicators

The following table shows the indicators that show the operating status of the controller and error information.

‹

Seven Segment Display

The following situations use the seven segment display:

• Manufacturing: During programming the seven segment display outputs "FLASH...". When finished, the seven

segment display outputs "donE".

• Startup: If the controller cannot boot because of a bad firmware image check sum, the seven segment display outputs

"bOOt ERROR".

• IP Address: If the TEST switch is ON, then the seven segment display outputs the IP address.
• Firmware update: During programming the seven segment display outputs "FLASH...". When finished, the seven

segment display outputs "donE".

Indicator

Color

Status

RDY

Green

Lit during normal operation.

RUN

Green

Lit during execution of user program.

ALM

Red

Lit/blinking when warning occurs.

ERR

Red

ON at initial power-up while firmware is loading. Turns off if
firmware is valid. Lit/blinking when malfunction occurs.

BAT

Red

Lit during battery alarm.

M-ALM

Red

Lit when a MECHATROLINK Communications Error occurs.

RDY

RUN

ALM

BAT

M-ALM

ERR