8 Base Unit Installation and Operating Conditions

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

15

8

Base Unit Installation and Operating Conditions

This section describes the specifications of the MP3200iec Series Machine Controllers.

Install the MP3200iec Series Controllers in an environment with the following conditions.

‹

Environmental Conditions

„

Control Panel Cooling Method

The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and
55°C. Use one of the methods described below to ensure adequate cooling in the control panel.

Note: If the ambient temperature exceeds 50°C, we recommend forced-air cooling.

Control Panels with Natural Cooling

• Do not mount the Machine Controller at the top of the control panel, where the hot air that is generated inside the panel

collects.

• Leave sufficient space above and below the Units, and maintain adequate distances from other devices, cable ducts, and

other objects to ensure suitable air circulation.

• Do not mount the Controller in any direction other than the specified direction.
• Do not mount the Controller on top of any device that generates a significant amount of heat.
• Do not subject the Controller to direct sunlight.

Control Panels with Forced-air Cooling

Use one of the following methods to ensure 0.03 m

3

/min average airflow below the CPU Unit.

• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.)
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.)

Note: Use the following guideline when selecting the fan: CPU Unit’s resistance to air flow: 6 x 10

6

(N×s

2

/m

8

)

Item

Specification

Ambient Operating Temperature

0 to 55°C (CPU-03: 0 to 50°C)

Ambient Storage Temperature

-25 to 85°C

Ambient Operating Humidity

30% to 95% RH (with no condensation)

Ambient Storage Humidity

5% to 95% RH (with no condensation)

Pollution Degree

Conforms to JIS B 3502 Pollution Degree 2.

Corrosive Gases

There must be no combustible or corrosive gases.

Operating Altitude

2,000 m max.