23 Option Module - LIO-04/05 Modules

66

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

‹

LIO-04 Digital Output Circuit (Sink Mode Output) Connection Example

‹

LIO-05 Digital Output Circuit (Source Mode Output) Connection Example

ON Time/OFF Time

ON: 0.5 ms Max
OFF: 1 ms Max

Number of Commons

1 per 8 outputs

Protection Circuit

The fuses are not for circuit protection. They are for fire protection at output shorts. Attach a fuse
externally to each output if circuit protection is required.

Fuse Rating

1A

Error Detection

Fuse blowout detection

Item

Specifications

0

24

+24V

Output
register

DO_OUT

0V

+24V

R

Photocoupler

R

Transistor

0

24

+24V

Output
register

DO_OUT

0V

+24V

R

Photocoupler

Transistor