Digital input circuit connection example, Digital output circuit connection example, Digital output circuit – Yaskawa MP3200iec User Manual

Page 80: 24 option module - lio-06 module

Advertising
background image

24 Option Module - LIO-06 Module

78

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

‹

Digital Input Circuit Connection Example

‹

Digital Output Circuit Connection Example

‹

Digital Output Circuit

The specifications of the LIO-06 digital output circuit are shown below.

Item

Specification

Number of Outputs

8

Output Method

Transistor Open Collector Sink Output

Isolation

Photocoupler Isolation

External Power Supply Voltage

DC24V±20%

Output Current

100mA Max

Leak Current at OFF

0.1mA Max

ON Time/OFF Time

ON=0.25ms Max/OFF=1ms Max

Number of Commons

1

Protection Circuit

The fuses are not for circuit protection. They are for fire protection at output shorts. A fuse
should be attached outside each output when a protective circuit is necessary.

Fuse Rating

1A

Error Detection

Blown fuse detection

Common

Internal Circuitry

Input
Register

DI

PS2805-4

1000PF

750

5.6

0.5

R

DO

Vin

Output

Register

R

FU

Photocoupler

PS280䠍䠉䠐

0䠲

Transistor

DTDS14GP

1.2k䃈

33k䃈

1000PF

Input Circuitry

Advertising