Analog input circuit, Analog input circuit connection example, Analog input characteristics response chart – Yaskawa MP3200iec User Manual

Page 81

Advertising
background image

24 Option Module - LIO-06 Module

YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5

79

‹

Analog Input Circuit

The specifications of the LIO-06 analog input circuit are shown below.

‹

Analog Input Circuit Connection Example

‹

Analog Input Characteristics Response Chart

The following shows an analog input response chart and input characteristics diagram for the LIO-06 module.

„

Input Characteristics Response Chart

• Minimum linearity of +10.0V cannot be assured.

Item

Specification

Analog Input Range

-10 to +10V

Number of Input Channels

1

Isolation

Non-isolated

Maximum Rated Input

±15V

Input Impedance

Approx. 20k

Ω

Resolution

16-bit (-31276 to +31276)

Accuracy

25ºC

±0.1%(±10mV)

0 to 55ºC

±0.3%(±30mV)

Input Filter

Time Constant

0.2×10

–2

Delay Time

1 ms (Max) (When -10+10V)

Conversion Speed

50

μs

DANGER

The time constant shows the characteristics according to the input filter equivalent to the time to reach 0.632 × the input
voltage.

Analog Input Value

Input Register Value

-10.5V

-32768

-10.0V

-31276

-5.0V

-15638

0.0V

0

+5.0V

15638

+10.0V

31276

+10.5V

32767

Ground

To A/D

Conversion

Internal Circuitry

Advertising