Drive start-up – Yaskawa VCD 723 User Manual

Page 33

Advertising
background image

2

Installation and Start-up

27

Drive Start-up

9/15/93

❏ Verify the motor, blower, thermistor, and PG (Digital Tachometer) wiring for

proper voltage and phase sequence. If the motor is a MagneTek Vector
Control Motor (VCM), then see the appendix for proper wiring. If the motor
is not a MagneTek VCM, then see the manufacturer supplied drawings.

❏ Apply three phase input power to the drive.

❏ Verify that the “CHARGE” lamp inside the drive is lit.

❏ The first message that will be displayed on the Local Control Display Unit is

the following:

Drive Start-up

Verifying the
CRC-16. Wait . . .

This is an indication that the CPU is verifying the program loaded in its
memory is valid. The check takes approximately 5 seconds. After the check,
one of a number of messages will be displayed.

❏ When the program and non-volatile memory is valid, the following message

will be displayed on the Local Control Display Unit:

Powered Up
and Ready

In addition, the Ready LED will be lit.

❏ The following is a list of abnormal display conditions that may occur, and

the actions necessary to correct the situation:

If there is an invalid program in memory, then the following message
will be displayed on the Local Control Display Unit:

Select BAUD rate
19200 UP,DWN,ENT

If this occurs, a new program must be uploaded into memory. See Section 3
for the proper program upload procedure.

Check that no faults are indicated on the drive’s display. A fault is
indicated by the Fault LED being lit and a fault message appearing on the
Local Control Display Unit. See Section 3 for more detailed information
regarding fault reporting and clearing.

Advertising