Troubleshooting/Maintenance

67

Troubleshooting Flowcharts

9/15/93

Chart 8. Overload (

oL

) Fault Indication

LOAD TOO LARGE

(MOTOR OVERHEATED)?

YES

YES

YES

YES

YES

DECREASE LOAD
WITHIN RATING.

CHECK MOTOR
AND LOAD.

CONSULT

FACTORY.

NO

NO

NO

NO

NO

WITH DRIVE IN
STOPPED CONDITION,
REPROGRAM PER PAC
DIAGRAM.

IS VCD 723 CAPACITY

FACTORY SET

CORRECTLY?

IS CORRECT

CURRENT RATING

DISPLAYED?

DISCONNECT WIRING FROM

OUTPUT TERMINALS T1(U),

T2(V) AND T3(W). IS OL

STILL INDICATED?

REMOVE NOISE SOURCE:

• CONNECT SURGE
SUPPRESSOR TO RELAY
AND MAGNETIC CON-
TACTOR COILS.

• PROVIDE LINE FILTER
TO REMOVE NOISE ON
INPUT POWER LINE.

CONTROL PCB,
OR BASE DRIVE
PCB IS FAULTY.
REPLACE FAULTY BOARD.

ERRONEOUS OPERATION

DUE TO NOISE?