Yaskawa VCD 723 User Manual

Page 76

Advertising
background image

4

Troubleshooting/Maintenance

70

Troubleshooting Flowcharts

9/15/93

Chart 11. Control Function Error (

CPF

) Fault Indication

1. CHECK THAT ALL DRIVE

HARNESS CONNECTORS,
AND CONTROL BOARD
MOUNTED PCB's, ARE
FIRMLY SEATED.

2. CHECK THAT CPU AND

EPROM ARE INSERTED
SECURELY.

3. CHECK THAT NO NOISE

SOURCE IS PRESENT.

4. REPROGRAM PER PAC

DIAGRAM USING
FACTORY RESET CODES.

5. CHECK Sn-01 AND Sn-02

FOR PROPER VALUES.

TURN OFF POWER. AFTER

"CHARGE" LAMP ON MAIN

PC BOARD GOES OUT,

TURN POWER BACK ON.

IS

CPF STILL

INDICATED?

IS

CPF STILL

INDICATED?

YES

YES

NO

NO

SELF-DIAGNOSIS FUNCTION
HAS DETECTED FAILURE IN
THE CPU OR PERIPHERAL
COMPONENTS.
REPLACE THE CONTROL PCB,
OR APPROPRIATE CONTROL
MOUNTED PCB.

DRIVE IS OK.
RETURN TO NORMAL
OPERATION.

Advertising