4

Troubleshooting/Maintenance

54

Fault and Error Conditions

9/15/93

ERROR/FAULT

PROBABLE CAUSE

CORRECTIVE ACTION

Replace braking transistor or gate drive
board.

Wait for resistor to cool. Check
application requirements for braking
capacity.

Verify proper wiring to the thermistor.
If properly wired, then use the spare
thermistor.

Verify that the correct version of
EPROM's are installed in the VCD 723.
This error indicates that the inverter
portion of the drive is programmed as a
VCD 703.

Verify that the correct version of
EPROM's are installed in the VCD 723.
This error indicates that the inverter
portion of the drive is programmed as a
VCD 703.

Verify wiring to PG-X circuit card CA-1
connector.

Verify all speed parameter settings (i.e.
pulses per revolution, motor rated
speed). Whenever changing parameter
settings the following procedure must
be followed:

Correct the setting.

Use function 994 to transfer the
data from RAM to NVRAM.

Turn power off.

When the charge light is off, then
turn power on.

Replace the inverter control circuit card.

Replace the inverter control circuit card.

Confirm that all parameters are within
allowable ranges. If they are, then
replace the inverter control circuit card.

Replace the inverter control circuit card.

Table 8. Standard Error and Fault Descriptions - Continued

703, BRAKE TRANSISTOR

704, BRAKE RESIST HOT

706, THERMISTOR OPEN

707, TRANSMIT ERROR

712, EXT FLT T INPUT

720, OPEN INV TACH

721, INV OVERSPEED

722, INV SPEED ERROR

741, BASE BLOCK CKT

742, SHADOW RAM FLT

743, NVRAM CHKSUM ERR

744, INV MCU Q/D FLT

Drive declared that the braking
transistor is malfunctioning.

Drive declared that the brake resistor
unit overheated.

Drive declared that the connection to
the motor thermistor is disconnected.

Drive declared that the transmission
between the VCD 723 and the remote
operator was not established within 5
seconds after the power supply was
turned on.

Drive declared that a transmission
error occurred 2 seconds after
transmission was established between
the VCD 723 and the remote operator.

Drive detected that its pulse generator
input is open.

Drive declared an overspeed.

Drive detected a probable speed error.

Drive detected a control circuit failure.

Drive detected that its NVRAM is bad.

Drive detected that the constants in its
non-volatile memory are not valid.

Drive detected that its CPU A/D
converter has failed.