COIL REG-No

Input the lead register number when performing link coil I/O with each station. Input the O register number of local
stations, and I register numbers for the other stations.

Set so that there is no register duplication between the stations.

CREG WORD

This sets the number of link register I/O words.

The maximum assignments per station is 256 words, combining links and coils.

COIL-No

This displays the lead coil numbers during link coil I/O. Input is not possible.
The register numbers input in COIL REG-No are displayed in the coil number format.

BIT

This displays the number of link coil I/O bits. Input is not possible. The number of link coil I/O words input in
CREG-WORD is shown in the number of bits.

SCAN

This selects the scan performing input and output between the CPU module and the PCLINK-01 from "High/Low".

In the case of a local station, there will be a transmission data output scan, and in the case of other stations, a
reception data input scan.

In the case of the local station, set the same scan as the SYNC-SCAN setting.

Station Name

Input the station comments in 32 characters.