When the transmission data address is duplicated, the data of the duplicated portion will be corrupted (Figure F3.1.2).

Perform assignment such that the transmission data addresses of each of the stations are not duplicated. This shows a
case where the output ranges of Station 3 and Station 2 are duplicated. (Although Station 3 normally assigns
OW0500~128 words, assignment of OW04C0~192 words is being performed. The 64 words of data shaded in the
figure are data corrupted due to overlap in Station 2 and Station 3.)














Figure F3.1.2 Address Duplication Link Map



Appendix 3.2

Settings at Remote Connection

The setting points for engineering communication via the MEMOBUS port of the PCLINK-01 module are as follows.


(1) Connection to GL120/130

Set the port selection as follows in cases of connection by MEMOSOFT.
• Set the protocol to "Link/Remote Receiver Port".
• For the address, set the PCLINK station number of the connection target GL120/130.
• Mode: Set RTU, Data Bits: 8, Parity: EVEN, Stop Bit: 1.
• Set the communication speed to 9600bps or 19200bps according to the serial transmission baud rate setting

switch of the PCLINK-01 module.

Figure F3.2.1 MEMOSOFT Port Selection Screen



Output

MP2XXX
PCLINK

GL120

PCLINK

Output

MP2XXX

PCLINK

Output

GL60

PCLINK

Station 1

Station 2

Station 3

Station 4

R10001

OW0000

IW0400

R0001

IW0080

IW0480

IW0100

IW0180

OW04C0

IW0580

R10129

R10257

R10385

R0129

R0257

R0385

Map in cases where the I/O lead address is 0000

Map in cases where the I/O lead address is 0400

Output

Advertising