Pclink, Serial – Yaskawa MP2000 Series User Manual

Page 31

Advertising
background image

Page 31

MP2000.02, 1/18/2011

Data subject to change without notice

Yaskawa America, Inc.

In addition, connection of a MEMOBUS master device to the serial port of the MP2000 series PCLINK-01 module

and MEMOBUS message communication via the PCLINK network are possible. The PCLINK–01 reception side has a
MEMOBUS message reception function. (When a MEMOBUS message is received via the serial port, CH5 is used by
the MSG-RCV function.) The controller on the transmission side does not need a ladder protocol. The MEMOBUS
messages received from the serial port will be automatically determined to be either received by the local CPU module
or transmitted on the PCLINK network according to the station address of the MEMOBUS protocol.




















Figure 4.4 MEMOBUS Messaging Between the Controllers via the PCLINK Serial Port


* In cases of a GL40, 60, 70 and GL120/130 side message slave, the message reception function can be omitted.

The MEMOBUS protocol capable of being used in PCLINK transmission is as follows.

Function Code

Meaning

Data Address Setting

Range

Data Size

MEMOBUS

01H

Coil Status Readout

0 ~ 65535

1~2000 (No. of bits)

02H

Input Relay Status Readout

0 ~ 65535

1~2000 (No. of bits)

03H

Holding Register Content Readout

0 ~ 65534

1~125 (No. of words)

04H

Input Register Content Readout

0 ~ 32767

1~125 (No. of words)

05H

Single Coil Status Change

0 ~ 65535

Disabled

06H

Write to Single Holding Register

0 ~ 65534

Disabled

08H Loopback

Test

Disabled Disabled

0FH

Multiple Coil Status Change

0 ~ 65534

1~800 (No. of bits)

10H

Write to Multiple Holding Registers

0 ~ 65534

1~100 (No. of words)

In PCLINK transmission, the transmission target can be designated by the group number in addition to the station

number in the message transmission target. In group number designation, it is possible to multicast messages to
stations with the same group number. However, the available messages are limited to the write series.

ÁÂÃÄÅÆÇÈÉ

Á

Â

Ã
Ä
Å
Æ

ÇÈ

ÁÂÃÄÅÆÇÈÉ

Á
Â

Ã
Ä
Å
Æ

ÇÈ

PCLINK





MEMOBUS command path

ÁÂÃ

ÄÂÅ

ÆÇÈ

ÁÂÃ

ÄÉ

ÆÇ

ÁÂÃÄ

É

ÆÇ

ÇÈ

Serial

MEMOBUS

Master Device

Serial

ÁÂÃÄ

ÂÅ

ÆÇÈ

Automatically
switches according to
the address number

É

É

The MEMOBUS protocol address
settings are transferred to the local
CPU if other than the PCLINK
station number address of the local
station

The MEMOBUS protocol address
settings are streamed on the PCLINK
network if other than the PCLINK
station number address of the local
station