MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 100 of 129

ProSoft Technology, Inc.

November 3, 2008

System Configuration Errors

Error
Code

Name Description

100

Too many binary input
points

Too many binary input points are configured for the module.
Maximum value is 7680

101

Too many binary output
points

Too many binary output points are configured for the module.
Maximum value is 7680

102

Too many counter
points

Too many counter points are configured for the module.
Maximum value is 240

103

Too many analog input
points

Too many analog input points are configured for the module.
Maximum value is 480

104

Too many analog input
points

Too many analog output points are configured for the
module. Maximum value is 480

105

Too many binary input
events

Too many binary input events are configured for the module.
Maximum value is 400.

106

Too many analog input
events

Too many analog input events are configured for the module.
Maximum value is 400.

107

Invalid analog input
deadband

Deadband value for analog input events is out of range.
Value must be in the range of 0 to 32767.

108

Not enough memory

There is not enough memory in the module to configure the
module as specified.

109

Invalid block transfer
delay for blocks
error/status blocks

Block transfer delay value specified is too low.

110

File count invalid

The file count must be in the range of 0 to 6.

111

Invalid file record size

The file record size must be in the range of 1 to 120.

112

Invalid block
identification code for
file

The file block transfer code must be in the range of 100 to
120.

DNP Port Configuration Errors

Error
Code

Name Description

212

Invalid DNP address

The DNP address specified in the configuration is not valid (0
to 65534).

213

Invalid DNP port baud
rate

The baud rate code specified in the configuration is not valid.

219

Invalid DNP data link
layer confirm mode

The data link confirmation mode code is not valid in the
configuration.

220

Invalid DNP data link
confirm time-out

The data link time-out period specified in the configuration is
0. It must be an integer in the range of 1 to 65535.

222

Invalid DNP
select/operate arm time
duration

The select/operate arm timer is set to 0. It must be an integer
in the range of 1 to 65535.

223

Invalid DNP application
layer confirm time-out

The application layer confirm time-out value is set to 0. It
must be an integer in the range of 1 to 65535.

224

Invalid DNP write time
interval

The write time interval is not in the data range in the
configuration. The value must be in the range of 0 to 1440.