ProSoft Technology MVI69-DNP User Manual

Page 101

Advertising
background image

Reference MVI69-DNP

♦ CompactLogix or MicroLogix Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 101 of 129

November 3, 2008

Error
Code

Name Description

225

Invalid DNP unsolicited
response mode

The unsolicited response mode code is not valid in the
configuration.

226

Invalid DNP unsolicited
response minimum
quantity for Class 1

The unsolicited response minimum quantity for Class 1 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.

227

Invalid DNP unsolicited
response minimum
quantity for Class 2

The unsolicited response minimum quantity for Class 2 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.

228

Invalid DNP unsolicited
response minimum
quantity for Class 3

The unsolicited response minimum quantity for Class 3 is not
valid in the configuration. Value must be an integer in the
range of 1 to 255.

230

Invalid DNP unsolicited
response destination
address

The unsolicited response destination address is not valid in
the configuration. Value must be in the range of 1 to 65534.

Command Error Codes

General Command Errors

Error
Code

Name Description

1 Device

not

defined

The IED slave address referenced in the command is not
defined in the module. Check to make sure there is an entry
in the slave table for each slave device referenced in the
command list.

2 Invalid

command

This command is not valid. Check to make sure the slave
address parameter is greater than or equal to zero and that
the point count is not set to zero.

3

Object not supported

The data object in the command is not supported by the
module. Refer to the DNP subset for the Master Port.

4

Command function not
supported

The function specified in the command is not supported for
the object type selected. Refer to the DNP subset for the
Master Port.

10

Invalid binary input poll
command

This binary input object command is not valid.

11

Invalid binary input
event poll command

This binary input event object poll command is not valid.

20

Invalid binary output
command function

This binary output command function is not valid.

30

Invalid counter poll
command function

The counter object poll command contains an invalid function
code.

31

Invalid counter poll
command

This counter object poll command is not valid.

40

Invalid frozen counter
poll command

This frozen counter object poll command is not valid.

50

Invalid analog input poll
command

This analog input poll command is not valid.

51

Invalid analog input
event poll command

This analog input event poll command is not valid.