Reference MVI69-DNP

♦ CompactLogix or MicroLogix Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 103 of 129

November 3, 2008

5.5 Internal

Indication

Word

5.5.1 First

Byte

Bit Description

0

All stations message received. Set when a request is received with the destination
address set to 0xffff. Cleared after next response. Used to let master station know
broadcast received.

1

Class 1 data available. Set when class 1 data is ready to be sent from the slave to
the master. Master should request class 1 data when this bit is set.

2

Class 2 data available. Set when class 2 data is ready to be sent from the slave to
the master. Master should request class 2 data when this bit is set.

3

Class 3 data available. Set when class 3 data is ready to be sent from the slave to
the master. Master should request class 3 data when this bit is set.

4

Time synchronization required from master. The master should write the date and
time when this bit is set. After receiving the write command the bit will be cleared.

5

Slave digital outputs are in local control. This bit is not used in this application.

6 Not

used

7

Device restart. This bit is set when the slave either warm or cold boots. It is cleared
after a master writes a 0 to the bit.

5.5.2 Second

Byte:

Bit Description

0

Bad function code. The function code contained in the master request is not
supported for the specified object/variation.

1

Requested object(s) unknown. Object requested by master is not supported by the
application.

2

Parameters in the qualifier, range or data fields are not valid or out of range for the
slave.

3

Event buffer(s) or other application buffers have overflowed. This bit is also set if the
slave receives a multi-frame message from the master.

4

Request understood but requested operation is already executing. The slave will
never set this bit.

5

Bad configuration. The slave configuration is invalid and should be re-configured. If
the configuration is invalid, the slave will set the invalid parameters to default values
and continue to run. Check error log using debug port.

6 Reserved,

always

0.

7 Reserved,

always

0.